Powerware 9135 Two-in-One UPS 5000/6000 VA User Manual

Page 59

Advertising
background image

OPERATION

EATON Powerware

®

9135 Two−in−One UPS (5000/6000 VA) User’s Guide

S 164201726 Rev 1

www.powerware.com

53

Table 4. Output Settings

Function

Factory Setting

Options

Comments

Output Voltage

EU Models: 230V
U Models: 208V

200V / 208V / 220V /
240V / 250V

Freq Converter

Disable

Enable

Output Frequency

EU Models: 50 Hz
U Models: 60 Hz

60 Hz

User selectable under
frequency−converter mode

Eco Mode

Disable

Enable

See page 50

Slew Rate

1 Hz / sec

0.5 Hz / sec

Bypass Transfer
If bypass Ac nok?

Yes

No

Transfer to bypass if utility power is
out of tolerance

Interrupt Time

10 ms

20 ms, ...... , 200 ms

Break time calibration during load
transfer on utility power out of
tolerance

Overload Prealarm

105%

40%, 50%, 70%

Alarm if threshold is overrun

Table 5. ON/OFF Settings

Function

Factory Setting

Options

Comments

Cold Start

Disable

Enable

Start on battery

Forced Reboot

Enable

Enables automatic restart of the
system even if utility power is
restored before the end of the
shutdown sequence

Auto Restart

Enable

Disable

UPS restarts automatically when
utility power is restored

Energy Saving

Disable

Enable

Automatic shutdown on battery if
output load level <10%

Sleep Mode

Enable

Disable

Remote Command

Enable

Disable

Enables consideration of shutdown or
restart orders from software to be
authorized