Relay port – Powerware 9135 Two-in-One UPS 5000/6000 VA User Manual

Page 65

Advertising
background image

ADDITIONAL UPS FEATURES

EATON Powerware

®

9135 Two−in−One UPS (5000/6000 VA) User’s Guide

S 164201726 Rev 1

www.powerware.com

59

Relay Port

When the status is active, the contact between the common (Pin 5) and
the relevant information pin is closed.

Output relays specifications:

S

Voltage: 48 Vdc maximum

S

Current: 2A maximum

S

Power: 62.5 VA, 30W

Example: for 48 Vdc, Imax=625 mA

Figure 36 identifies the cable pins and Table 9 describes the pin
functions.

NOTE Normally−open (NO)

Normally−closed (NC)

Common

NC

NO

NO

NO

NO

7

8

6

9

3

5

4

2

1

Figure 36. Communication Port

Table 9. Communication Port Pin Assignment

Pin Number

Function

1, 2

Not used

3

Remote Power−off signal (5–27 Vdc, 10 mA max)

4

Operation on mains (not on battery)

5

User common

6

Operation on automatic bypass

7

Low Battery

8

Load protected

9

Operation on battery

Advertising