4.4.2 Specifications

Table 4-1: Specifications

Isolation

2.5 kV optoisolated towards the system

Input

8 channels (80 V AC - 264 V AC)
Common neutral
< 0.5 mA input current
Input frequency range
Overvoltage protection (continu-
ous):
Switch-ON delay:
Switch-OFF delay:
High level:
Low level:

47-63 Hz
350 V AC
< 21 ms
< 16 ms
> 20 V
< 10 V

Front panel

Green LEDs (switched on, when INPUT is active)

Options

User-configurable RC filter on the last channel for INTx
generation

Power con-
sumption

3 mW min., 70 mW max.

Temperature
range

Standard:0° C to +70° C
Extended:-40° C to +85° C

Module weight

38 g

ID Byte

$02, read by the SPI interface