9 isagraf programming, 1 the isagraf board parameters, 9 isagraf programming -56 – Pepper Computer Modular Computers RS485 User Manual

Page 212: 1 the isagraf board parameters -56, Smart i/o user’s manual, Chapter 5 analog modules

Advertising
background image

SMART I/O User’s Manual

March 12, 1996

©1996 PEP Modular Computers GmbH

Page 5 - 56

Chapter 5 Analog Modules

5.2.9 ISaGRAF Programming

5.2.9.1 The ISaGRAF Board Parameters

Information on board parameters may be found in the PEP online help and

ISaGRAF online help or user’s manual.

Figure 5.2.9.1.1 a Typical Screen Section for the SM-PT100 Module

Logical Address

The 4 inputs of this module may be clearly seen together with the logical

address at which this particular board is residing. Remember, this logical

address is the same as the physical slot position! In the example shown here,

the board being addressed is in slot 3 i.e. the third of the SMART-BASE

slots. Up to 11 slots are catered for in the SMART I/O concept; 3 on the

SMART-BASE and 2 for each connected SMART-EXT (up to a total of 4).

Module Specific Information :

calib_period

:

This is the time in seconds for cyclic calibration if

required. An entry of zero disables the function.

type_ch(x)

:

This parameter is either

resistor100

or

PT100

depending whether the returned value should be raw

ohmic or calibrated in degrees Celsius respectively.

Advertising
This manual is related to the following products: