Smart i/o user’s manual, Chapter 5 analog modules – Pepper Computer Modular Computers RS485 User Manual

Page 184

Advertising
background image

SMART I/O User’s Manual

March 12, 1996

©1996 PEP Modular Computers GmbH

Page 5 - 28

Chapter 5 Analog Modules

O_DISABLE_CONV

: This operate call tells ISaGRAF to disable the

conversion of a particular channel of a connected

SM-DAD1 module. The syntax is as follows:

<analog var> := OPERATE(<iovar>, O_DISABLE_CONV, 0);

where

<analog var>

represents the analog return variable and can

be zero if the operate call is supported and the

correct

<iovar>

is passed or non-zero if an

error occurred.

<iovar>

is the variable name for the channel where the

operate call is to take effect.

Advertising
This manual is related to the following products: