4 smadcsetcycliccalib, 4 smadcsetcycliccalib -41 – Pepper Computer Modular Computers RS485 User Manual

Page 197

Advertising
background image

SMART I/O User’s Manual

©1996 PEP Modular Computers GmbH

March 12, 1996

Page 5 - 41

5

Chapter 5 Analog Modules

5.2.8.4 SMADCSetCyclicCalib

Syntax

error_code SMADCSetCyclicCalib(u_int8 PortNr, u_int

secs);

Description

This function sets the time between two calibration cycles in seconds. If

secs=0, then cyclic calibration is disabled.

Input

u_int8 PortNr

Port number of module for calibration

(from 0 to 10)

u_int16 secs

Time in seconds between two calibration

cycles

Output

error_code

SUCCESS

E_MNF

If wrong type of module or no module

is fitted on the selected port

or standard OS-9 error code (refer to the OS-9

Technical Manual Error Codes Section).

Example

RetVal = SMADCSetCyclicCalib(0 , 120);

Advertising
This manual is related to the following products: