Raypak 500 User Manual

Page 22

Advertising
background image

22

*

* - May be configured as DHW SENSOR for

single boiler Cascade with Indirect

Fig. 18: XFyre Cascade Master

Cascade Master Pump and

Sensor Wiring

1. On the boiler designated as the Cascade Master,

apply the System Sensor and DHW Sensor decals

(included) to the field wiring board as shown in Fig.

18. Apply the SYSTEM PUMP and EXT HEATER

labels to the wiring electrical connections terminal

strip as shown in Fig. 11b on page 17.

2. Connect the system pump hot wire to terminal #11,

marked SYSTEM PUMP (see Fig 11b).

3. Connect the system pump neutral to terminal #6,

marked BOILER PUMP NEUT, and the pump

ground wire to terminal #3, marked GROUND, at

the rear terminal strip.

4. Connect a jumper wire from terminal #1, marked

120 V BLACK (HOT), terminal #11, marked SYS-

TEM PUMP POWER, at the rear terminal strip.

5. Connect the boiler pump to the terminals marked

BOILER PUMP NEUT (#6), BOILER PUMP HOT

(#5), and GROUND (#4).

6. Connect the system pipe sensor to the terminals

marked SYS SENSOR, as shown in Fig. 18.

7. Connect the outdoor sensor (if used) to the termi-

nals marked OUTDOOR SEN.

8. Connect the signal to start the system to the termi-

nals marked THERMOSTAT.

NOTE: This signal can come from a room

thermostat or a dry contact closure. No power of any

voltage should be fed into either of these terminals.

Fig. 19: XFyre Cascade Follower

Advertising
This manual is related to the following products:

300, 850