Maintenance, Suggested minimum maintenance schedule, Preventive maintenance schedule – Raypak 500 User Manual

Page 49

Advertising
background image

49

MAINTENANCE

Suggested Minimum

Maintenance Schedule

Regular service by a qualified service agency and

maintenance must be performed to ensure maximum

operating efficiency.

Maintenance as outlined below may be performed by

the owner.

Daily

1. Check that the area where the boiler is installed is

free from combustible materials, gasoline, and

other flammable vapors and liquids.

2. Check for and remove any obstruction to the flow

of combustion or ventilation air to boiler.

Monthly

1. Check for piping leaks around pumps, mixing

valves, relief valves, and other fittings. If found,

repair at once. DO NOT use petroleum-based

stop-leak compounds.

2. Visually inspect burner flame.

3. Visually inspect venting system for proper func-

tion, deterioration or leakage.

4. Visually inspect for proper operation of the con-

densate drains in the venting, and the internal

condensate trap. Clean trap as necessary. If leaks

are observed, repair at once.

5. Check air vents for leakage.

Yearly (Beginning Of Each Heating

Season)

Schedule annual service call by qualified service

agency.

1. Visually check top of vent for soot. Call service

person to clean. Some sediment at bottom of vent

is normal.

2. Visually inspect venting system for proper func-

tion, deterioration or leakage. Ensure that

condensate drain is inspected and ensure that

condensate is being directed to appropriate con-

densate management system or drain, as required

by local codes.

3. Check that area is free from combustible materi-

als, gasoline, and other flammable vapors and

liquids.

4. Check for and remove any obstruction to the flow

of combustion or ventilation air to boiler.

5. Follow pre-start-up check in the Start-up section.

6. Visually inspect burner flame. It should be light

blue at full input. Remove and visually inspect

direct spark igniter and sensor for damage, crack-

ing or debris build-up.

7. Check operation of safety devices. Refer to manu-

facturers’ instructions.

8. Follow oil-lubricating instructions on pump (if re-

quired). Over-oiling will damage pump.

Water-lubricated circulators do not need oiling.

9. To avoid potential of severe burn, DO NOT REST

HANDS ON OR GRASP PIPES. Use a light touch;

return piping will heat up quickly.

10. Check blower and blower motor.

11. Check for piping leaks around pumps, relief valves

and other fittings. Repair, if found. DO NOT use

petroleum-based stop-leak.

Periodically

1. Check relief valve. Refer to manufacturer’s

instructions on valve.

2. Test low water cut-off (if equipped). Refer to manu-

facturer’s instructions.

Preventive Maintenance

Schedule

The following procedures are recommended and are

good practice for all XFyre installations.

Daily

1. Check gauges, monitors and indicators.

2. Check instrument and equipment settings. (See

“Post Start-Up Check”.)

Advertising
This manual is related to the following products:

300, 850