Controls – Raypak 500 User Manual

Page 32

Advertising
background image

32

Controls

WARNING: Installation, adjustment and service of

controls, including timing of various operating func-

tions, must be performed by a qualified installer,

service agency or the gas supplier. Failure to do so

may result in control damage, malfunction, property

damage, personal injury, or death.

WARNING: Turn off the power to the boiler before

installation, adjustment or service of any controls.

Failure to do so may result in board damage,

malfunction, property damage, personal injury, or

death.

CAUTION: This appliance has provisions to be

connected to more than one supply source. To

reduce the risk of electric shock, disconnect all such

connections before servicing.

CAUTION: Risk of electric shock: More than one

disconnect switch may be required to de-energize

the equipment before servicing.

Ignition Control Functions

When there is a call for heat, the combustion air blow-

er starts to purge air from the combustion chamber.

After the pre-purge, the igniter is energized. The stan-

dard ignition module will lock out after failing to light

four times or after losing flame three times during a

single heat demand. To reset it, press and release the

ESC/RESET button located on the user interface. The

control will automatically reset after 1 hour. When in

lock out, the control will run the blower for a 1 minute

purge cycle. Turning off the power to the heater

WILL NOT reset the ignition module.

The optional single-try ignition module will attempt to

light only one time before locking out. To reset it, press

the ESC/RESET button on the user interface.

High Limit — Manual Reset

This boiler is equipped with a fixed-setting manual re-

set high limit temperature device as standard or it may

have an optional adjustable setting manual reset high

temperature device.

The fixed-setting manual-reset high limit is located on

the outlet pipe of the heat exchanger on the left side of

the boiler (accessible through the front door for reset

as necessary).

Fig. 26: High Limit (Manual Reset)

High Limit — Auto Reset (Optional)

This heater is equipped with a fixed auto-reset high

limit temperature device.

The optional auto reset high limit is located on the heat

exchanger header, near the outlet.

Fig. 27: High Limit (Auto Reset)

NOTE: Each ignition module is specific to a single

model size. Care should be taken not to use a mod-

ule intended for a different model size.

Advertising
This manual is related to the following products:

300, 850