Direct Vent—Vertical

Installation

These installations utilize the heater-mounted blower

to draw combustion air from outdoors and vent com-

bustion products to the outdoors.

* Subtract 10 ft per elbow. Max. 4 elbows.

Table O: Category IV Horizontal Vent & Horizontal Direct Vent

The total length of air supply pipe cannot exceed the

distances listed in Table L. Each elbow used is equal

to 10 ft of straight pipe. This will allow installation in

any arrangement that does not exceed the lengths

shown in Table L.

The vent cap is not considered in the overall length of

the venting system.

Care must be taken during assembly that all joints are

sealed properly and are airtight.

The vent must be installed to prevent the potential ac-

cumulation of condensate in the vent pipes. It is

required that:

1. The vent must be installed with a condensate

drain as directed by the vent manufacturer.

2. The vent must be installed with a slight upward

slope of not more than 1/4 inch per foot of hori-

zontal run to the vent terminal.

Termination

The vent cap MUST be mounted on the exterior of the

building. The vent cap cannot be installed in a well or

below grade. The vent cap must be installed at least 1

ft above ground level and above normal snow levels.

The vent cap MUST NOT be installed with any com-

bustion air inlet directly above a vent cap. This vertical

spacing would allow the flue products from the vent

cap to be pulled into the combustion air intake installed

above.

CAUTION: This venting system requires the

installation of a condensate drain in the vent piping

per the vent manufacturer’s instructions. Failure to

install a condensate drain in the venting system will

void all warranties on this boiler.

Fig. 24: Direct Vent - Vertical

Model No.

Certified Vent

Material

Vent and

Intake Air

Vent Size

(in.)

Horizontal Vent Height

(ft)

Combustion

Air Intake

Pipe

Material

Air Inlet

Max.

Length (ft)*

Min.

Max.

300

(Canada Only:

ULC-S636 PVC

and CPVC)

Stainless Steel,

AL29-4C,

ANSI/ASTM D1785

Sch 40 PVC,

ANSI/ASTM F441

Sch 40 CPVC

4

0

100

Galvanized

Steel,

PVC, ABS,

CPVC

100

500

850

6

Advertising
This manual is related to the following products:

300, 850