Table L: Category IV Vertical Vent & Vertical Direct Vent

1

Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details.

* Subtract 10 ft per elbow. Max. 4 elbows.

Termination

The vent terminal should be vertical and should termi-

nate outside the building at least 2 ft above the highest

point of the roof that is within 10 ft. The vent cap

should have a minimum clearance of 4 ft horizontally

from and in no case above or below (unless a 4 ft hori-

zontal distance is maintained) electric meters, gas

meters, regulators and relief equipment.

Fig. 20: Vertical Venting

Installation

The maximum and minimum venting length for this

Category IV appliance shall be determined per the

NFGC (U.S.) or B149 (Canada).

The diameter of vent flue pipe should be sized accord-

ing to the NFGC (U.S.) and Appendix B of B149

(Canada). The minimum flue pipe diameter for con-

ventional venting is: 4 in. (102mm) for Models 300 and

500, and 6 in. (152mm) for Model 850.

The connection from the appliance vent to the stack

must be as direct as possible and shall be the same di-

ameter as the vent outlet. The horizontal breaching of

a vent must have an upward slope of not less than 1/4

inch per linear foot from the heater to the vent termi-

nal. The horizontal portions of the vent shall also be

supported for the design and weight of the material

employed to maintain clearances and to prevent physi-

cal damage or separation of joints.

NOTE: A vent adapter (field-supplied) may be re-

quired to connect the Category IV vent to the boiler.

Model No.

Certified Vent

Material

Vent and

Intake Air

Vent Size

(in.)

Vertical Vent Height

1

(ft)

Combustion

Air Intake

Pipe

Material

Vertical Air

Inlet Max.

Length* (ft)

Min.

Max.

300

(Canada Only:

ULC-S636 PVC

and CPVC)

Stainless Steel,

AL29-4C,

ANSI/ASTM D1785

Sch 40 PVC,

ANSI/ASTM F441

Sch 40 CPVC

4

0

100

Galvanized

Steel,

PVC, ABS,

CPVC

100

500

850

6

The distance of the vent terminal from adjacent public

walkways, adjacent buildings, open windows and

building openings must be consistent with the NFGC

(U.S.) or B149 (Canada). Vents supported only by

flashing and extending above the roof more than 5 ft

should be securely guyed or braced to withstand snow

and wind loads.