Outdoor installation – Raypak 500 User Manual

Page 31

Advertising
background image

31

This type of installation can cause non-warrantable

problems with components and poor operation of the

boiler due to the recirculation of flue products. Multi-

ple vent caps installed in the same horizontal plane

must have a 4 ft clearance from the side of one vent

cap to the side of the adjacent vent cap(s).

Combustion air supplied from outdoors must be free of

particulate and chemical contaminants. To avoid a

blocked flue condition, keep the vent cap clear of

snow, ice, leaves, debris, etc.

The stainless steel flue direct vent cap must be fur-

nished by the boiler manufacturer in accordance with

its listing (sales order option D-15).

Outdoor Installation

Outdoor models must be vented with listed vent mate-

rial per the following instructions and installed with the

optional factory-supplied outdoor vent kit. A special

vent terminal is provided in accordance with CSA

requirements. These must be installed as illustrated in

Fig. 25.

Care must be taken when locating the unit outdoors,

because the flue gases discharged from the vent cap

can condense as they leave the cap. Improper location

can result in damage to adjacent structures or building

finish. For maximum efficiency and safety, the follow-

ing precautions must be observed:

1. Outdoor models must be installed outdoors and

must use the outdoor vent cap available from the

manufacturer (sales order option D-11).

2. Periodically check venting system. The unit’s

venting areas must never be obstructed in any

way and minimum clearances must be observed

to prevent restriction of combustion and ventilation

air. Keep area clear and free of combustible and

flammable materials.

3. Do not locate adjacent to any window, door, walk-

way, or gravity air intake. The vent must be

located a minimum of 4 ft horizontally from such

areas.

4. Install above grade level and above normal snow

levels.

5. Vent terminal must be at least 3 ft above any

forced air inlet located within 10 ft.

6. Adjacent brick or masonry surfaces must be pro-

tected with a rust-resistant sheet metal plate.

Freeze Protection

The Raypak electronic temperature control includes a

freeze protection feature. In the event the temperature

drops below 40°F at any of the temperature sensors,

the pump is turned on and will remain on until the tem-

peratures at all sensors rise to 45°F.

WARNING: No substitutions of flue pipe or vent

cap material are allowed. Such substitutions would

jeopardize the safety and health of inhabitants.

NOTE: The vent cap must be furnished by the boiler

manufacturer in accordance with its listing (sales

order option D-11).

NOTE: Condensate can freeze on the vent terminal.

Frozen condensate on the vent terminal can result in

a blocked flue condition.

Fig. 25: Outdoor Venting

Model

No.

Size

(in.)

Approved

Plastic

Terminals

Approved SS

Terminals

300

4

PVC Tee,

Sch 40*

FasNSeal FSTT4,

Z-Vent 2SVSTTF04

500

850

6

PVC Tee,

Sch 40*

FasNSeal FSTT6, Heat

Fab 9690TEE

Table P: Outdoor Vent Terminals

*Must be ULC-S636 materials in Canada.

Advertising
This manual is related to the following products:

300, 850