23

English Translation by: Tribotix Pty Ltd

www.tribotix.com

DYNAMIXEL

DX-116

5. Example

Used to explain through example with the assumption that the Dynamixel has

been Reset (ID = 1, Baudrate = 57142BPS)

Example 5

Read the Model Number and Firmware Version of a Dynamixel with ID=1


Instruction Packet

Instruction = READ_DATA,

Address = 0x00, Length = 0x03


Communication

->[Dynamixel]:FF FF 01 04 02 00 03 F5 (LEN:008)

<-[Dynamixel]:FF FF 01 05 00 74 00 08 7D (LEN:009)

Status Packet Result Model Number = 116(0x74), Firmware Version = 0x08

Example 6

Change ID number of Dynamixel from 1 to 0.


Instruction Packet

Instruction = WRITE_DATA, Address = 0x03, DATA = 0x00


Communication

->[Dynamixel]:FF FF 01 04 03 03 00 F4 (LEN:008)

<-[Dynamixel]:FF FF 01 02 00 FC (LEN:006)

Status Packet Result NO ERROR

Example 7

Change Baud Rate of Dynamixel to 1M bps.


Instruction Packet

Instruction = WRITE_DATA, Address = 0x04, DATA = 0x01


Communication

->[Dynamixel]:FF FF 00 04 03 04 01 F3 (LEN:008)

<-[Dynamixel]:FF FF 00 02 00 FD (LEN:006)

Status Packet Result NO ERROR

Example 8

Reset Return Delay Time of Dynamixel with ID=0 to 4us.

A Return Delay Time Value of 1 corresponds to 2us.

Instruction Packet

Instruction = WRITE_DATA, Address = 0x05, DATA = 0x02


Communication

->[Dynamixel]:FF FF 00 04 03 05 02 F1 (LEN:008)

<-[Dynamixel]:FF FF 00 02 00 FD (LEN:006)

Status Packet Result NO ERROR