SECTION 5: MAJOR COMPONENTS
5.1 General
Heaters are designed for installation above 6'
(1.8 m). These heaters must be installed within the
heated space. Duct delivery systems are not
permitted with axial fan units. When handling or
supporting the heater from below, ensure that the
weight is taken at the support points.

5.2 Suspension

For typical suspension, See Page 6, Figure 2.

Figure 2: Suspension Methods

WARNING

Crush Hazard

Use 3/8" threaded rod

minimum.

Failure of the supports can

result in death, injury

or property damage.

Cone Point

Set Pin

Window

Clamp

Unistrut

3/8"

Threaded

Rod

Nut

Washer

Riv

Nut

Support Points

Ensure all suspension

hardware is torqued to

a minimum of 20 ft lbs.

Washer

3/8"

Threaded

Rod

Nut

Unistrut

Channel Nut