Warning – Roberts Gorden Tubular Unit Heaters 300 User Manual

Page 42

Advertising
background image

COMBAT

®

UHA U

NIT

H

EATER

I

NSTALLATION

O

PERATION

AND

S

ERVICE

M

ANUAL

36

14.7 Pressure Switch
Pull off 3 way connector. Spring open plastic clips of mounting cradle. Replace with correct type of

pressure switch for model. The pressure switches are color coded for each pressure setting.

Carry out a commission after working on or changing a pressure switch. See Page 19, Section 10.

14.8 Ignition Control
The control mounts to the electrical plate. Pull out ignition cable and wiring from board, noting their
positions.

Release the four mounting standoffs.

Refit in reverse. Ensure correct location of ignition cable and all other wiring.

14.9 Axial Fan/Guard/Motor Assembly
The axial fan unit for the heater is supplied completely assembled and balanced

Carbon Monoxide Hazard

Use correct pressure switch specified for each model.

Use of incorrect pressure switch or disabling

pressure switch circuit could cause unsafe condition.

Failure to follow these instructions can result in

death or serious injury.

WARNING

MODEL

UHA[S]

150 - 175

UHA[S]

200 - 225

UHA[S]

250

UHA[S]

300 - 350

UHA[S]

400

Pressure Switch
Kit P/N

90439802

90439808

90439803

90439807

90439808

Color Code

yellow

orange

gray

brown

orange

Set Point in. w.c.

.32

.79

.41

.68

.79

Pressure Switch Snap
Ring P/N

90439850

90439850

90439850

90439850

90439850

MODEL

UHA[S] 150 - 175

UHA[S] 200- 250

UHA[S] 300 - 400

Axial Fan Guard

91901105

91901104

91901105

Axial Fan Motor

90600106

90600107

90600106

Axial Fan Blade

90709005

90709006

90709005

Advertising