Roberts Gorden Tubular Unit Heaters 300 User Manual

Page 43

Advertising
background image

SECTION 14: R

EPLACEMENT

P

ARTS

37

14.9.1 Fan Removal and Replacement

14.9.2 To Replace the Fan Assembly

• To replace the fan assembly, reverse the

procedure shown above.

• Check that the fan blades are free to rotate

before turning on the power to the fan.

• Strictly comply with the color code of the fan

wires to ensure correct operation.

See Page 16, Section 9.3 wiring diagram.

• Use only genuine replacement parts sold and

supplied by Roberts-Gordon

14.10 Limit Switches
14.10.1 Removal and Replacement

1. Remove the electrical connections to the

switch.

2. Unscrew the two screws securing the switch.

3. Fit a new switch with two screws.See Page 39,

Section 15.3

.

4. Reconnect the electrical connections and test

operation.

Description

Part Number

Qty.

Axial Fan UHA[S] 150 - 175

90710416

1

Axial Fan UHA[S] 200 - 250

90710417

1

Axial Fan UHA[S] 300 - 400

90710416

2

Remove the screws

and washers.

Remove the mounting hardware.