Warning, Heater – Roberts Gorden Tubular Unit Heaters 300 User Manual

Page 52

Advertising
background image

10'

(3 m)

WARNING

© 2007 Roberts-Gordon, LLC www.rg-inc.com Printed in U.S.A. P/N 91040031 Rev B

Attach this information to the wall near the ROBERTS GORDON

®

heater

Read the Installation, Operation and Service Manual thoroughly before installation, operation or service.

OPERATING INSTRUCTIONS

1. STOP! Read all safety instructions on this information sheet.
2. Open the manual gas valve in the heater supply line.
3. Turn on electric power to the heater.
4. Set the thermostat to desired setting (above ambient temperature).
The automatic starting sequence begins.

1.Turn the thermostat/time switch to 'OFF' or lowest setting. The burner
will turn 'OFF' immediately, but fans will continue to cool heat exchanger
until the fan thermostat switches off.

1.Set the thermostat to off or the lowest setting.
2.Turn off electric power to the heater.
3.Turn off the manual gas valve in the heater supply line.
4.Call your installer/contractor qualified in the installation and service

of gas-fired heating equipment.

IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,

FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER

Fire Hazard

Some objects can catch fire or explode when placed

close to heater.

Keep all flammable objects, liquids and vapors the

required clearances to combustibles away from heater.

Failure to follow these instructions can result in death,

injury or property damage.

TO TURN OFF THE HEATER

Roberts-Gordon, LLC

1250 William Street

P.O. Box 44

Buffalo, NY 14240-0044 USA

®

Left

Right

Bottom

Top

Clearances to Combustibles

Wall

Terminal

Roof Terminal

Max. Mounting Height*

Rear*

Installation Clearances

Installation Code and Annual Inspections:

All installations and service of ROBERTS GORDON

®

equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and

conform to all requirements set forth in the ROBERTS GORDON

®

manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help

facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON

®

equipment and perform service where necessary,

using only replacement parts sold and supplied by Roberts-Gordon.
For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.

Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON

®

representatives. Please

contact us for any further information you may require, including the Installation, Operation and Service Manual.

Models 100-400 are not for residential use.

Telephone: 716.852.4400

Fax: 716.852.0854

Toll Free: 800.828.7450

*Models

Top

Rear

Max Mounting Height

30 - 125

1" (2.5 cm)

18" (46 cm)

12' (3.7 m) - 20' (6 m)

150 - 400

6" (15 cm)

24" (61 cm)

20' (6 m) - 30' (9 m)

Heaters can be mounted higher if destratification fans are installed. See Installation, Operation

and Service Manual for specific mounting height recommendations.

NOTE: Venting directly from top of heater not applicable on Models 150-400.

Models
Top
Bottom
Right
Left
Vent

30 - 125

1" (2.5 cm)

0" (0 cm)

1" (2.5 cm)

18" (46 cm)*

2" (5 cm)

150 - 400

6" (15 cm)

3" (8 cm)

31" (79 cm)*

6" (15 cm)

2" (5 cm)

* Clearance needed for servicing.

Top

Bottom

Right

Left

Models 30 - 125

Models 150 - 400

(Optional separated

combustion concentric

venting shown.)

Top*

1

1