Warning, Installation, Thermostat wiring diagrams – Rinnai 37AHB SERIES User Manual

Page 18

Advertising
background image

18

Rinnai Corporation Hydronic Furnace (37AHB) Manual

Shunt Jumper Options:
An additional feature of the 37AHB series is its
selectable operating sequence option; the 3-pin shunt
header (P7) allows the control to operate the proper
heating logic based on the following system
requirements:

The 37AHB unit in Open Loop configuration:

“FS” Shunt selection: The “FS” logic sequence will
configure the unit for operation with all Rinnai®
Tankless Water Heaters; this logic monitors the ratio
of available flow for space heating (via Flow Sensor);
this status is then communicated to the PCB whose
operating characteristics is primarily determined by the
status of the Flow Sensor input (sequence allows
domestic priority).

Failure to follow this warning could result in an
electrical shock, fire, or death.
To minimize personal injury if an electrical fault should
occur, cabinet grounding MUST be an uninterrupted
ground and MUST comply with NEC, ANSI/NFPA 70
and all local codes having jurisdiction. The ground
may consist of electrical wire or metal conduit when
installed in accordance with existing electrical codes.

WARNING

THERMOSTAT WIRING DIAGRAMS

Installation

FIRST STAGE HEAT/COOL

AUX HEATING

FAN

24VAC HOT

24 VAC COMMON

SINGLE STAGE

HYDRONIC FURNACE

SINGLE SPEED

CONDENSING

UNIT

HEAT/COOL & COOL ONLY

THERMOSTATS

Y1

W

G

R

C

Y1

Y2

W

G

O

R

C

Y1

C

Single Stage Hydronic Furnace w/ Single Stage A

Figure 16

FIRST STAGE HEAT/COOL

AUX HEATING

FAN

RVS COOLING

24VAC HOT

24 VAC COMMON

HEAT PUMP THERMOSTATS

SINGLE STAGE

SINGLE STAGE

HEAT PUMP

Y1

W

G

O

R

C

Y1

W

G

O

R

C

Y1

O

R

C

Y2

Figure 17

Single Stage Hydronic Furnace
w/ Single Stage Heat Pump

FIRST STAGE HEAT/COOL

SECOND STAGE HEAT/COOL

AUX HEATING

FAN

24VAC HOT

24 VAC COMMON

HEAT/COOL & COOL ONLY

THERMOSTATS

SINGLE STAGE

TWO STAGE

CONDENSING

UNIT

Y1

Y2

W

G

R

C

Y1

Y2

W

G

O

R

C

Y1

Y2

C

Figure 18

Single Stage Hydronic Furnace w/ Two Stage A/C

FIRST STAGE HEAT/COOL

SECOND STAGE HEAT/COOL

AUX HEATING

FAN

RVS COOLING

24VAC HOT

24 VAC COMMON

HEAT PUMP THERMOSTATS

SINGLE STAGE

TWO STAGE

HEAT PUMP

Y1

Y2

W

G

O

R

C

Y1

Y2

W

G

O

R

C

Y1

Y2

O

R

C

Figure 19

Single Stage Hydronic Furnace
w/ Two Stage Heat Pump

HYDRONIC FURNACE

HYDRONIC FURNACE

HYDRONIC FURNACE

Advertising