Rinnai Corporation Hydronic Furnace (37AHB) Manual

Installation

Figure 20:

Hydronic Furnace Start-Up and ‘LED’ Troubleshooting - Flow Sensor (FS Configuration)

NOTES:

1 Pipe system between Tankless Water Heater and Hyronic Furnace ‡
2 Leak check piping system
3 Purge and prime plumbing system
4 Perform required electrical work
5 Check system operation with power to condensing unit off (if installed)
6 Control board is sometimes refered to as 'PCB'
7 Hyronic Furnace is sometimes refered to as 'RHF'
8 Typical for all check, ensure system is in the following operating mode:

AC / SINGLE STAGE

9 For Amp loads refer to specification sheet
10 Thermostat is sometimes refered to as 'T'STAT'

‡ Refer to plumbing section in this manual

NO

YES

IS 'LED' ON

WITH DOOR SWITCH CLOSED

(SET SYSTEM IN HEATING

MODE - CALL FOR HEAT)

YES

NO

START

SYSTEM

PURGED

CHECK

VOLTAGE ACROSS'L1'

AND 'L2'

RETURN TO PURGE & PRIME

STEPS ‡

IS 'LED'

RAPIDLY

FLASHING

STEADY 'LED' FLASH - NORMAL

OPERATION OR STAND-BY

MODE AWAITING

THERMOSTAT CALL

YES

NO

DOMESTIC HOT WATER

DEMAND PRESENT –SYSTEM

ON HOLD

- SEARCH MODE

IS 'LED' RAPID

FLASH

CONSISTENT

YES

INCONSISTENT RAPID FLASH (PULSATING

PUMP OPERATION)– WRONG SHUNT

POSITION

- REFER TO FIG.14 HYDRONIC

FURNACE CONTROL BOARD, JUMPER

(SHUNT) POSITION'P7' TO BE IN 'FS'

MODE

NO

CHECK

BREAKER AND POWER

SUPPLY

IS POWER

SUPPLY OK

YES

NO

RECTIFY

SUPPLY VOLTAGE

PROBLEM(S) ANDRETURN TO

START

VAC = 115V +/-

NO

CHECK

DOOR SWITCH, IF

DEFECTIVE, REPLACESAME

AND RETURN TO START

YES

GO TO

24 VOLTS

TROUBLESHOOTING CHART

CHECK

FOR LOOSE OR

BROKEN WIRE

CHECK

SYSTEM WIRING

AGAINST WIRING DIAGRAM -

RECTIFY PROBLEM(S)

L1/L2 = 115V +/-

NO

YES

IS 'LED' ON

NO

YES