Installation, Figure 23 – Rinnai 37AHB SERIES User Manual

Page 23

Advertising
background image

Rinnai Corporation Hydronic Furnace (37AHB) Manual

23

Installation

Figure 23:

24V Troubleshooting - Flow Sensor (FS) Configuration

24V BETWEEN THERMOSTAT AND PCB

24V BETWEEN CONDENSING UNIT AND PCB

If a condensing unit and cased coil set is used in conjunction with the Rinnai Hydronic Furnace for cooling,
refer to air conditioning manufacturer's instructions for hook-up and troubleshooting details.

NO

FINISH

ENSURE THAT T'STAT IS IN

HEATING

MODE AND RECHECK

FOR CONTINUITY

NO

NO

YES

CONTACT

TECH. SUPPORT

SYSTEM

WORKING

YES

NO

WITH DOOR SWITCH CLOSED

(SET SYSTEM IN HEATING

MODE -CALL FOR HEAT)

START

IS 'LED' ON

YES

NO

PRI:VAC = 115V +/-

SEC: VAC = 24V +/-

YES

NO

GO TO

HYDRONIC FURNACE START UP

AND 'LED' TROUBLESHOOTING

VAC = 24V +/-

YES

CHECK

3 AMP

FUSE; IS FUSE

INTACT

(1) CHECK FOR

WIRING PROBLEM(S)

(2) CHECK

TRANSFORMER; IF DEFECTIVE,

REPLACE

FAULTY COMPONENT

(1) CHECK

FOR WIRING PROBLEM(S)

(2) CHECK

FUSE; IF DEFECTIVE,

REPLACE

FAULTY COMPONENT

IS THERE

CONTINUITY

AT

T'STAT

CHECK

T'STAT FOR CONTINUITY

WITH OHM METER BETWEEN

'R' AND 'W'

YES

IS THERE

CONTINUITY

AT

T'STAT

YES

CHECK THERMOSTAT;

IF

DEFECTIVE REPLACE

COMPONENT

CHECK

FOR 24 V ACROSS

'WH/FS'

PINS

CHECK PCB;

IF DEFECTIVE

REPLACE

COMPONENT AND

RETURN TO START

NO

CHECK

FOR WIRING

PROBLEM(S) AND REPAIR OR

REPLACE AND RETURN TO

START

CHECK

TRANSFORMER FOR

CORRECT

VOLTAGES