Rinnai Corporation Hydronic Furnace (37AHB) Manual

59

Accessories

FIELD SUPPLIED ACCESSORIES

1. Humidifier (HUM)

Connect an auxiliary 2.5 FLA, 2.5 LRA @ 115 VAC

max Humidifier (if required). Connections are
made via the “HUM” quick connects. The humidifier
output is on whenever a heating demand is being
satisfied. The contacts of this output are isolated to
allow field personnel to apply 24 VAC or 115 VAC
to one terminal and the humidifier load to the other.

2. Electronic Air Cleaner (EAC)

Connect an auxiliary Electronic Air Cleaner (if

required); rating shall be max 1.0 Amp @ 115
VAC. This output is energized whenever any of the
four blower speeds are energized. Connections
are made via 0.250 x 0.032” male quick connect
terminals labeled "EAC" and "N3".

3. UV Lamp

Connect an auxiliary UV lamp (if required); rating

shall be max 1.0 Amp @ 115 VAC. This output is
energized whenever any of the four blower speeds
are energized. Connections are made via 0.250 x
0.032” male quick connect terminals labeled "UV"
and "N2"

4. Filter Rack & Bottom Fill Plates

Refer to Figures 3 and 4 in this manual and the

table below:

5. Thermostats

The Standard Model thermostat is an electronic

24 vac, programmable, manual changeover wall
-mount thermostat. This thermostat uses two set
points to maintain and control room temperature in
both the heating and air conditioning modes. The
thermostat is designed to maintain +/-2°F accuracy.
No batteries are required; temperature, blower,
mode, and installer configuration settings are
preserved with power off.

6. Flow Sensor

Refer to the plumbing section of this manual for

installation instructions. The sensor is packaged
with the hydronic furnace in the literature bag
affixed between the filter and filter retention wire.

7. Anti-scald Thermostatic Temperature Control

Valve

Anti-scald thermostatic temperature control valves

are an important part of domestic water plumbing
because they eliminate the scalding and cold water
shocks that can occur in a shower when a toilet is
flushed or a faucet is turned on. In an Open Loop
system (dual function – space heating and
domestic water heating), an anti-scald valve should
be installed when the Tankless Water heater set
thermostat is above 120°F (49°C); refer to local
codes and/or all authority having jurisdiction. For
recommended piping configuration refer to Figure
11. Anti-Scald valve shall be thermostatically
controlled and meet at least the following
specifications:

Dual certification ASSE 1016-T and ASSE 1017

IAPMO Approved

CSA Approved

Constant water temperature under different

operating conditions.


An approved anti-scald/anti-chill thermostatic

temperature control valve is available through the
Rinnai® Accessory Program.

Part Part

Number

Thermostatic Mixing Valve

603000016

Sensor, Flow Actuated

603000010

Part Part

Number

Bottom Fill Plate 37AHB045 603000011
Bottom Fill Plate 37AHB060

603000012

Bottom Fill Plate 37AHB075 603000013
Bottom Fill Plate 37AHB090 603000014
Side Filter Rack 37AHB

603000015

Part Model

Part

Number

Part Part

Number

AC Thermostat

603000018

Heat Pump Thermostat