Selection guide, Maintenance – Rinnai 37AHB SERIES User Manual

Page 27

Advertising
background image

Rinnai Corporation Hydronic Furnace (37AHB) Manual

27

Figure 24:

Hydronic Furnace and Tankless Water heater Sizing Guidelines

Selection Guide

4. Install new motor, and reassemble circulator using

the new gasket and bolts supplied.

5. Follow the “installation” procedure to start up the

circulator.

Replacing Pump Cartridge Assembly:

1. Disconnect the electrical supply.

2. Reduce system pressure to 0 psi and allow system

to return to room temperature. Isolate the circulator
by closing the service valves or draining the
system.

3. Remove the body bolts and swing motor assembly

away from the volute.

4. Pull cartridge out of the motor housing.

5. Install replacement cartridge, making sure that the

cover plate is between the cartridge flange and
motor.

6. Make sure the replacement cartridge corresponds

to the full circulator product number. A complete
parts list is available from your local distributor.

7. Reassemble the circulator using the new gasket

and bolts supplied.

8. Follow the “Installation” procedure to start up the

circulator.

Replacing Pump Capacitor:

1. Replacement capacitor must have same rating as

originally furnished.

Maintenance

Advertising