9. DATA FORMAT:

This is one byte and specifies the data which will be transmitted against the
"V01" command.

Bit pattern:

bit 0 = 0/1

Means do not include/include peak & valley status register.

bit 1 = 0/1

Means do not include/include reading.

For models(TC/RTD/ACV/ACC):

bit 2 = 0/1

Means do not include/include peak reading.

For models(PR/ST):

bit 2 = 0/1

Means do not include/include process totalize.

For models(TC/RTD/ACV/ACC):

bit 3 = 0/1

Means do not include/include valley reading.

For models(PR/ST/FP):

bit 3 = 0/1

Means do not include/include peak reading.

For models(TC/RTD/ACV/ACC):

bits 4

Not used. Set to 0.

For models(PR/ST/FP):

bits 4 = 0/1

Means do not include/include valley reading.

bit 5

Not used. Set to 0.

bit 6 = 0/1

Means do not include/include unit of measure.

bit 7 = 0/1

Means space/carriage return between values.

10. DEVICE ADDRESS :

This is one byte data and specifies the address of the unit when in RS485 multipoint mode.
Addresses are in hexadecimal from 01 to FF.

NOTE:

Address 00 is for broadcasting. All units on the same BUS will perform any
command with this address but will not respond.

11. RECOGNITION CHARACTER:

This is one byte security character.
(Default is *)