Communication Parameter Settings:

Communication settings information are very critical during set-up, if any of the parameters are
changed, it should be recorded on the label for future reference. If the communication parameters
used by the computer does not match the communication parameter of the DRX, then the
communication link may not be established. Hence it is important to record the communication
parameter on the label if different from default.

Resetting Communication Parameters to Factory Defaults

To restore the communication parameters to the factory default settings, two test points must be
shorted together. There are two ways of shorting these test points together, both are detailed below.

Version A-- Test point TP6 must be shorted, by a wire, to test point TP17.

or

Version B-- Newer units have a jumper position S1-A for connecting these two test points together.

Factory Default Settings for Communication:

Baud Rate = 9600
Data Bit = 7
Parity = Odd
Stop Bits = 1
Recognition Character = *
Address = 01

Page 3

DRX -- SIGNAL CONDITIONERS WITH RS485

SERIAL COMMUNICATION PORT

COMPUTER

RS232 TO

RS485 CONVERTER

HALF—DUPLEX

NOTE: YOU CAN CONNECT A DRX
DIRECTLY TO THE COMPUTER IF YOU
HAVE A RS485 COMMUNICATION
CARD INSTALLED IN THE COMPUTER.

SYSTEM GND

OR SHIELD

FIRST UNIT ON BUS

LAST UNIT ON BUS

TEE COUPLER

(JACKS SHOWN

FOR CLARITY)

SHIELDED WIRE

CONNECT LAST
UNIT WITH
JUMPER TO
INCLUDE 120

ON THE BUS

DIN RAIL

Advertising