Omron Programmable Terminals NT631C User Manual

Page 116

Advertising
background image

99

Connecting to the Host’s RS-422A/485 Port

Section 5-2

C1000H/C2000H Rack-mounting Unit: C500-LK203

Setting the Rear Switches

C200H/C1000H/C2000H CPU-mounting Unit: 3G2A6-LK202-EV1

Setting the Rear Switches

I/O port

RS-422A

RS-232C

Synchronization

Internal

External

Terminator

OFF

ON

CTS

0 V

External

• I/O port selection (selector switch)

Set this to RS-422A.

• Synchronization (selector switch)

Set this to Internal.

• Communications speed

(DIP SW2-1 to SW2-4)

• 1-to-1/1-to-N selection (DIP SW2-6)

Set SW2-6 to OFF (0) (1-to-N).

• Instruction level (DIP SW2-7, SW2-8)

Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)

5 V supply

ON

OFF

• Unit #, parity, and transfer code

(DIP SW1-1 to SW1-7)

Set SW1-1 to SW1-7 to OFF (0).

• CTS selection (selector switch)

Set this always to 0 V (ON).

• Terminator setting (selector switch)

Set this switch to ON.

SW1

SW2

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

ON

ON

Set these switches to 1010 to select
9,600 bps.
(0: OFF 1: ON)

Set these switches to 0010 to select
19,200 bps.

SW1

SW2

SW3

• Unit #, parity, and transfer code

(DIP SW1-1 to SW1-5)
Set SW1-1 to SW1-5 to OFF (0).

• Communications speed (DIP SW2-1 to SW2-4)

Set these switches to 0010 to select 19200 bps.
Set these switches to 1010 to select 9600 bps.
(0: OFF 1: ON)

• 1-to-1/1-to-N selection (DIP SW2-6)

Set SW2-6 to OFF (0) (1-to-N).

• Instruction level (DIP SW2-7, SW2-8)

Set these switches to ON (1).
(Levels 1, 2, and 3 are enabled.)

• Terminator setting (DIP SW3-1 to SW3-6)

Set SW3-1, SW3-3, and SW3-5 to ON (1).
Set SW3-2, SW3-4, and SW3-6 to OFF (0).
(Set terminator ON.)

* Parity is fixed at Even Parity. Transfer code

is fixed at ASCII 7 data bits and 2 stop bits.