1-4 grounding, Grounding – Omron Programmable Terminals NT631C User Manual

Page 51

Advertising
background image

34

Installation

Section 3-1

Power Supply

The applicable power supply specifications are as follows.

Parts Used for Connection

Note

For the connection to the power supply terminal block, twisted wires of 2 mm

2

or greater cross sectional area and M3.5 size crimp terminals must be used.

Tighten the screws on the terminal block to a torque of 0.8 N

⋅m.

Recommended Terminals

Note

Conformance to Shipbuilding Standard

• Cover the entire PT with electromagnetic shielding, and ground the elec-

tromagnetic shielding to the control panel with copper tape or other elec-
trically conductive tape.

Recommended electromagnetic shielding: E09F100 or E09R13502P

Manufacturer: Seiwa Electric MFG, Co., Ltd.

• Use gaskets or other materials to completely shield all openings and

other gaps in the control panel.

• Use copper tape or other electrically conductive tape to shield gaps

between the cutout and the PT before securing the PT in place.

• To suppress noise terminal voltage, perform installation under the follow-

ing conditions. It is recommended to use the following product for the DC
power supply.
Recommended Power Supply model: S82K-03024
Manufacturer: OMRON

3-1-4

Grounding

The NT631/NT631C has a functional ground terminal (

).

Carry out wiring under the following conditions.

Item

Value

Power supply

24 VDC

Allowable power supply voltage

fluctuation range

20.4 to 26.4 VDC (24 VDC –15% to +10%)

Power supply voltage capacity

NT631-ST211 (B)-EV2:

30 W or more (Power supply warm-up time
within 200 ms.)

NT631C-ST141 (B) /ST153 (B)-EV3:

18 W or more

Maker

Type

(fork type)

Type

(round type)

Applicable Wire

(stranded wire)

Japan Solderless Terminal MFG

2-YS3A

2-3.5

2.0 to 2.63 mm

2

Fuji Terminal

2-YAS3.5

V2-S3.5

Nichifu Terminal

2Y-3.5

2-3.5

Fork type

Round type

7 mm max.

7 mm max.