Connecting to the Host’s RS-422A/485 Port

Section 5-2

*3

CPU Units of CVM1/CV-series PLCs without the suffix -EV

@ cannot be

connected.

The NT Link (1:1) method cannot be used using RS-485. To use the NT Link
(1:1) method, connect by RS-422A.

The 1:1 NT Link connection using RS-422A/485 is not possible with the
CPM1, CPM2A, or CPM2C.

Settings at the Host

The setting methods for each type of Unit are described in the following.

• Connecting to a CVM1/CV-series (-EV

@) CPU Units

• CV500-CPU01-EV1/CV1000-CPU01-EV1/CV2000-CPU01-EV1

• CVM1-CPU01-EV2/CVM1-CPU11-EV2/CVM1-CPU21-EV2

PLC Setup

When connecting to a CVM1/CV-series CPU Unit by the NT Link (1:1)
method, no particular settings are required at the PLC Setup.

Setting the Front Switches

• Connecting to a C-series C200HX/HG/HE(-Z)E

PLC Setup Area Settings

Write the PLC Setup area (data memory) settings directly from a Program-
ming Device (e.g. CX-Programmer) in accordance with the host model.

*1

RS-422A port of the Communications Board

*2

RS-422A port of the Serial Communications Board

For details on operations relating to the PLC Setup area, refer to the manual
for the PLC you are using.

Host Model

Word #

Setting

Setting Contents

Port A of C200HX/HG/HE(-Z)E

*1

DM6555

4000

Use NT Link (1:1)

Port 2 of CQM1H

*2

DM6550

4000

• Host link communications method selection

(selector switch)

Set this to RS-422A.

• Terminator setting (DIP SW6)

Set this switch to ON.
(Set terminator ON.)

I/O port selector switch

RS-422A

RS-232C

• Communications type setting (DIP SW3)

Set this switch to ON.
(for communications by NT Link)