136

Memory Initialization

Section 6-4

Reference:

• When this function is used, all of the screen data contents registered in

the NT631/NT631C up to that point are cleared. Check that the created
screens are backed up at the Support Tool before using it.

• The screen data can be cleared in the System Installer mode too

(page 148).

• The following types of data can be initialized individually.

Contents of numeral/character string memory tables (page 141)

Memory switch settings (page 143)

Display history record data (page 137)

Alarm history record data (page 138)

Clear the screen data by following the menu operation from the System Menu
shown below.

Select Maintenance Mode.

Select Memory Init..

Select Screen Data.

Select Yes.

Ver 4.12

The screen data is cleared. During
clearance, the message Erasing Now...
is displayed.