2-5 1:n connection among rs-485 ports, N connection among rs-485 ports – Omron Programmable Terminals NT631C User Manual

Page 138

Advertising
background image

121

Connecting to the Host’s RS-422A/485 Port

Section 5-2

Note

A Serial Communications Board cannot be installed.

For details on handling shield wires, refer to 5-2-8 Handling the Shield on RS-
422A/485 Cables
on page 125.

5-2-5

1:N Connection among RS-485 Ports

The connection method in which the RS-485 ports of multiple NT631/
NT631Cs and one host are connected in a 1:N connection is described here.

Reference:

• Communications using the RS-485A standard NT link (1:N) method is

possible only when a Serial Communications Board is installed in a CS-
series PLC, a Serial Communications Unit is installed in a CS/CJ-series
PLC, a Communications Board is installed in a C200HX/HG/HE(-Z)E, or a
CQM1H-SCB41 Serial Communications Board is installed in a CQM1H.

• Communications using the RS-485A high-speed NT link (1:N) method is

possible only when a Serial Communications Board is installed in a CS-
series PLC or a Serial Communications Unit is installed in a CS/CJ-series
PLC.

C200HX-CPU65-ZE/85-ZE

CQM1H-CPU51/61

6

5

9

1

NT631/NT631C side

Shielding wire

PLC side

Pin number

1

2

3

4

5

6

7

8

9

(9-pin type)

RDA

TRM

RDB

SDA

SDB

RSA

RSB

24V
+DC

Abbreviation

RDA (-)

TRM

RDB (+)

SDA (-)

SDB (+)

RSA (-)

RSB (+)

Next PT

Abbreviation

FG

SDA (-)

SDB (+)


RDA (-)

RDB (+)

RS-422A
interface

RS-422A/
485
interface

Functional
ground

Connector
hood

NT631/NT631C

9-pin connector

CPU Unit

NT631/NT631C

NT631/NT631C

RS-485 cables
(max. total length 500 m)

Serial port B
(RS-422A/485, terminal block)

CS/CJ-series or
C200HX/HG/HE(-Z)E
PLC