67

Connecting to the RS-232C Port at the Host

Section 4-1

Reference:

Version 1 (-V1) and high-speed versions (H) of the CS-series and CJ-series
CPU Units support the high-speed 1:N NT Link method in addition to the
standard 1:N NT Link method. Furthermore, the high-speed 1:N NT Link
method can be used in earlier versions of CS-series CPU Units by installing
the latest version of a Serial Communications Board or Unit. For details, refer
to Using the High-speed NT Link (1:N) Method (page 70).

Settings at the Host

The Settings required for each Unit are described below.

• Connecting a C-series C200HX/HG/HE(-Z)E, CQM1H, or SRM1

PLC Setup Area Settings
Write the PLC Setup area (data memory) settings directly from a Program-
ming Device (e.g. CX-Programmer) in accordance with the host model and

port.

*1

RS-232C port on the Communications Board

*2

RS-232C port on the Serial Communications Board

*3

When using a C200HE(-Z)E, the maximum PT unit number is 3.

Refer to the PLC’s operation manual for details on changing PLC Setup set-
tings.

Setting the DIP Switches of a C200HX/HG/HE(-Z)E
When using a C200HX/HG/HE(-Z)E, the DIP switches on the front panel must
be set as shown below in order to make the settings in the PLC Setup area
(data memory) effective.

Connecting to CS/CJ-series CPU Units

CS/CJ-series CPU Unit: CS1G/H-CPU

@@-E(V1), CS1G/H/D-CPU@@H,

CJ1G/M-CPU

@@, CJ1G/H-CPU@@H

Connect the PT to the CPU Unit’s built-in RS-232C port. Use a CS1W-CN118
Connecting Cable, however, if connecting the PT to the peripheral port of the
CPU Unit.

PLC Setup Area Settings
When connecting to a CS/CJ-series CPU Unit, set the following communica-
tions conditions for the PLC Setup area, in accordance with the communica-
tions port to be used.

Connection to

Word #

Writing

Value

Setting

C200HX/HG/HE(-Z)E, SRM1

Built-in RS-232C port

DM6645

5

@00

Use NT link (1:N)

@ = highest unit number of
the connected PTs (1 to 7)

(*3)

C200HX/HG/HE(-Z)E

Communications Board port A

*1

CQM1H port 1

*2

DM6555

C200HX/HG/HE(-Z)E

Communications Board port B

*1

DM6550

RS-232C port communications condition setting
Set DIP SW5 to OFF to make the settings made in
PLC Setup effective.