Omega Speaker Systems RH/Temperature Transmitter HX93A User Manual

Page 10

Advertising
background image

6

9. RH Measured Vs Output Reading

10. Temperature Output Calculations

To calculate Temperature by measuring the current or voltage output
use the following formulas.
For Current output in ºC (-20 to 75ºC)
ºC = (Output measured in miliamps – 4) ÷ .1684 - 20 = ºC
EXAMPLE:

(12.0 mA – 4) ÷ .1684 - 20 = 27.5ºC

For Current output ºF (-4 to 167ºF)
ºF = (Output measured in miliamps – 4) ÷ .0935 - 4 = ºF
EXAMPLE:

(12.0 mA – 4) ÷ .0935 - 4 = 81.6ºF

For Voltage output in ºC (-20 to 75ºC)

ºC = (Output measured in volts ÷ .010526) - 20 = ºC

EXAMPLE:

(0.50 Vdc ÷ .010526) - 20 = 27.5ºC

For Voltage output ºF (-4 to 167ºF)
ºF = (Output measured in volts ÷ .005848) - 4 = ºF
EXAMPLE:

(0.50 Vdc ÷ .005848) - 4 = 81.5ºF

% Relative

Output

Humidity

Current (mA)

Voltage (Vdc)

5 4

0.8

.05

10

5.6

.10

15

6.4

.15

20

7.2

.20

25

8.0

.25

30

8.8

.30

35

9.6

.35

40

10.4

.40

45

11.2

.45

50

12.0

.50

55

12.8

.55

60

13.6

.60

65

14.4

.65

70

15.2

.70

75

16.0

.75

80

16.8

.80

85

17.6

.85

90

18.4

.90

95

19.2

.95

9

HX93A, HX93DA SERIES
RH/Temperature Transmitter