FUEL UNITS AND OIL LINES

SINGLE-PIPE OIL LINES Standard burners are

provided with single-stage 3450 rpm fuel units with the

by-pass plug removed for single-pipe installations.

The single-stage fuel unit may be installed single-pipe

with gravity feed or lift. Maximum allowable lift is 8

feet. See Figure 15.

TWO-PIPE OIL LINES For two-pipe systems

where more lift is required, the two-stage fuel unit is

recommended. Table 4 (single-stage) and Table 5 (two-

stage) show allowable lift and lengths of 3/8-inch and

1/2-inch OD tubing for both suction and return lines.

Refer to Figure 16.

Be sure that all oil line connections are absolutely

airtight. Check all connections and joints. Flared

fittings are recommended. Do not use compression

fittings.

Open the air-bleed valve and start the burner. For clean

bleed, slip a 3/16" ID hose over the end of the bleed

valve and bleed into a container. Continue to bleed for

15 seconds after oil is free of air bubbles. Stop burner

and close valve.

Figure 15

Figure 16

Lift "H"

(See Figure)

Maximum Length of Tubing

"H" + "R" (See Figure)

3/8" OD

Tubing (3 GPH)

1/2" OD

Tubing (3 GPH)

0'

84'

100'

1'

78'

100'

2'

73'

100'

3'

68'

100'

4'

63'

100'

5'

57'

100'

6'

52'

100'

7'

47'

100'

8'

42'

100'

9'

36'

100'

10'

31'

100'

11'

26'

100'

12'

21'

83'

13'

---

62'

14'

---

41'

TABLE : SINGLE STAGE UNITS (50 RPM)

TWO PIPE SYSTEMS

Lift "H"

(See Figure)

Maximum Length of Tubing

"H" + "R" (See Figure)

3/8" OD

Tubing (3 GPH)

1/2" OD

Tubing (3 GPH)

0'

93'

100'

2'

85'

100'

4'

77'

100'

6'

69'

100'

8'

60'

100'

10'

52'

100'

12'

44'

100'

14'

36'

100'

16'

27'

100'

18'

---

76'

TABLE 5: TWO-STAGE UNITS (50 RPM)

TWO-PIPE SYSTEMS