The New Yorker Store Cast Iron-Oil Fired Boiler CL User Manual

Page 26

Advertising
background image

26

Figure 2: Setpoints and Differentials

System Condition

Diagnostic Condition

Check

Action

Boiler is cold, house is

cold.

Display is OFF.

120 Vac System power.

Turn system power on.

Display is ON.

24 Vac T-T

No 24 V; replace control.

24 V present; disconnect

thermostat, short T-T.

Boiler starts, check wiring and thermostat.

120 Vac at B1-B2

• If no, replace control.

• If yes, check burner and wiring.

Refer to

Err on display.

-----

Boiler is hot, house is

cold.

Display is ON.

120 Vac at C1-C2

• 120 Vac at C1-C2, check wiring

to pump.

• Wiring OK, is pump running?

• If not, replace the pump.

• If pump is running, check for

trapped air or closed zone valves

Boiler below the Low Limit

temperature, wait for boiler to go

above Low Limit temperature.

-----

Boiler above LL? If yes, check

for 120 Vac between ZC and L2.

• If no 120 Vac , replace control.

• If yes, check zone relays, circulators

and wiring.

TABLE 8: TROUBLE SHOOTING GUIDE

7. HIGH LIMIT CONTROLLER

The High Limit opens and turns off the burner

when the water temperature reaches the setpoint.

The High Limit automatically resets after the water

temperature drops past the setpoint and through the

Differential. The L7248 models have High Limit

Differential presets of 15°F (8°C). The L7224

models have High Limit Differential presets of 10°F

(6°C).

8. LOW LIMIT AND CIRCULATOR CONTROLLER

On a temperature rise, with the adjustable

Differential at the default setting of 10°F (6°C),

the burner circuit breaks and the circulator circuit

makes (assuming no call for heat is present) at the

Low Limit setpoint. On a temperature drop of 10°F

(6°C) below the Low Limit setpoint, the burner

circuit makes and the circulator circuit breaks. See

Figure 24.

F.

REMOVE GUN ASSEMBLY

1. CL Series boilers are equipped with Beckett AFG

burners. Items to be checked are nozzle size, head

size, gun setting, and positioning of electrodes. This

information is shown in Figure 25 and Table 9 at

rear of manual.

2. CL Series boilers are equipped with Carlin EZ-HP

burners. Items to be checked are nozzle size, head

bar size, gun setting, and positioning of electrodes.

This information is shown in Figure 25A and Table

9 at rear of manual.

3. Reinstall gun assembly.

Figure 25: "L1" and "V1" Head Electrode

Positioning and Gun Setting (Beckett AFG)

Advertising