Beckett afg, Carlin burner – The New Yorker Store Cast Iron-Oil Fired Boiler CL User Manual

Page 46

Advertising
background image

6

TABLE 9: BURNER SPECIFICATIONS

Beckett AFG

Boiler Model Firing Rate

GPH

Settings

Nozzle



Pump

Pressure

Head

(Setting)

Air

Shutter

Air

Band

GPH x Angle Type

2

Shipped

1

CL3-091

0.65

L1

8

0

0.55 x 70B (Delavan) p Loose

140

CL3-105

0.75

L1

6

0

0.65 x 45B (Hago)

p

Loose

140

p

CL3-140

1.00

L1

10

1

0.85 x 45B (Hago)

Installed

140

CL4-126

0.90

L1

7

0

0.75 x 45B (Delavan) Installed

140

CL4-175

1.25

V1(0)

10

1

1.00 x 45B (Hago)

Loose

175

CL4-210

1.50

V1(0)

10

2

1.10 x 45B (Hago)

Installed

175

CL5-168

1.20

V1(2)

10

0

0.90 x 45B (Hago)

l

Loose

175

l

CL5-245

1.75

V1(3)

7

3

1.35 x 45B (Hago)

Installed

175

CL5-280

2.00

V1(4)

10

3

1.50 x 45B (Hago)

Installed

175

Carlin Burner

Boiler Model Firing Rate

GPH

Burner

Model

Settings

Nozzle



Pump

Pressure

Head

Bar

Air

Band

GPH x Angle Type

2

Shipped

CL3-091

0.65

EZ-1HP

0.50

0.55

0.55 x 70B (Delavan) p Loose

150

CL3-105

0.75

0.60/0.65

0.60

0.60 x 60ES (Hago)

p

Loose

150

p

CL3-140

1.00

0.85/1.00

0.75

0.85 x 60B (Hago)

Installed

150

CL4-126

0.90

0.75

0.75

0.75 x 60A (Delavan)  Loose

150

CL4-175

1.25

0.85/1.00 1.00-1.10 1.00 x 60A (Delavan)  Loose

150

CL4-210

1.50

1.10/1.25 1.25-1.35

1.25 x 60B (Hago)

Installed

150

CL5-168

1.20

0.85/1.00

0.90

1.00 x 60B (Hago)

Installed

150

CL5-245

1.75

EZ-2HP

1.50

1.75

1.50 x 60A (Delavan) Installed

150

1

Beckett low firing rate baffle required on CL3-091 (0.65 GPH) application only; shipped loose with nozzle.

2

Nozzle(s) for alternate boiler model firing rate(s) are shipped loose in bag attached to the

burner designated by corresponding symbol, i.e. (p) = CL3-140.



Single stage fuel pump is standard, two stage fuel pump is optional. Burner manufacturer has preset

single stage fuel pump to settings shown in table above.