Figure 26: Adjusting Fuel Pump Pressure

Figure 25A: Electrode Settings (Carlin EZ-HP)

G.

ADJUST OIL BURNER BEFORE STARTING.

1. SET BURNER AIR BAND AND AIR SHUTTER,

see Table 9 at rear of manual.

2. Inspect Beckett head setting on left side of burner

by insuring the blue line MD(V1) or the line on the

label MB(L1) are aligned, readjust if necessary.

Refer to Figure 25.

3. Inspect Carlin head setting on left side of burner to

ensure that the proper head positioning bar matches

the nozzle that is installed in drawer assembly.

Replace bar if necessary.
Carlin burners for boiler models CL3-140 and

CL4-210 have the higher firing rate nozzle installed

and two (2) loose nozzles with a head positioning

bar kit attached to the nozzle line. Refer to Table

9 for proper nozzle size, air settings and fuel pump

pressure setting based on desired firing rate.

If the desired firing rate is the lower GPH:

a. replace the factory installed high firing rate

nozzle with one of the loose lower firing rate

nozzles.

b. replace the factory installed head positioning bar

with the corresponding head bar that matches the

lower GPH nozzle installed, see Table 9.

c. change the factory air settings according to Table

9 and,

d. check the oil pump pressure and adjust if

necessary to the setting specified in Table 9, refer

to Paragraph H, Step 5 for details.

4. INSPECT RIELLO BURNER AIR DAMPER

AND TURBULATOR SETTING, readjust if

necessary, see Table 9a.
a. Remove pressure port/bleeder plug from fuel

pump and install Riello Combination Pressure

Gauge and Bleeder Valve Assembly.

5. OPEN ALL OIL LINE VALVES.
6. ATTACH A PLASTIC HOSE TO FUEL PUMP

VENT FITTING and provide a pan to catch the oil.

7. OPEN FLAME OBSERVATION DOOR on front of

boiler.

H.

START OIL BURNER.

1. Open vent fitting on fuel pump.
2. TURN ‘ON’ BURNER service switch and allow

burner to run until oil flows from vent fitting

in a SOLID stream without air bubbles for

approximately 10 seconds.

3. Close vent fitting and burner flame should start

immediately after pre-purge is complete. Pre-purge

prevents burner flame until 15 seconds has elapsed

after initial power is applied to burner. During

pre-purge, the motor and ignitor will operate but the

oil valve will remain closed. Refer to Oil Primary

Control Instructions for more details.

4. ADJUST OIL PRESSURE for Beckett AFG burners

(shut the burner off).
a. When checking a fuel unit's operating pressure, a

reliable pressure gauge may be installed in either

the bleeder port or the nozzle port. See Figure

26.

b. Locate oil pressure adjusting screw and turn

screw for appropriate pump pressure, refer to

Table 9 at rear of manual.

c. To check the cutoff pressure, deadhead a reliable

pressure gauge onto the copper connector tube

attached to the nozzle port. Run the burner for

a short period of time. Shut the burner off. The

pressure should drop and hold.

d. Remove the gauge and install bleeder port and/or

reconnect the nozzle port line.

5. VERIFY/ADJUST FUEL PUMP PRESSURE for

Carlin EZ-HP burners.
a. Turn “off” burner service switch.