Iii. indirect water heater piping – The New Yorker Store Cast Iron-Oil Fired Boiler CL User Manual

Page 23

Advertising
background image

2

III. Indirect Water Heater Piping

A.

CONNECT Link SL™ or other Indirect Water Heater Piping as shown in Figures 15 and 16. Refer to Link SL™ or other

Indirect Water Heater Instruction Manual for additional installation information.

Figure 20: Indirect Water Heater Piping on CL Series Water Boiler

1. CL SERIES WATER BOILER - Figure 20 shows indirect water heater piping on typical hot water heating system. Boiler

piping is the same as for any two-zone system. Figure 20 shows circulator zoning, which is usually preferred for indirect

water heaters. Size the circulator and indirect water heater piping to obtain the boiler water flow through the indirect

water heater called for by the indirect water heater manufacturer. Refer to the indirect water heater instruction manual for

additional details.

Figure 21: Indirect Water Heater Piping on CL Series Steam Boiler

2. CL SERIES STEAM BOILER - All CL Series steam boilers are equipped with tappings to permit the connect of an

Link SL™ or other indirect water heater. In this type of system, hot boiler water is drawn from below the water line and

passed through the heat exchanger in the indirect water heater. This section describes boiler-side piping only. Refer to the

indirect water heater instruction manual for additional details.

Advertising