Notice – The New Yorker Store Cast Iron-Oil Fired Boiler CL User Manual

Page 31

Advertising
background image

1

iv. Stop feeding water to boiler but continue

operating oil burner until excess water in

boiler flows out through supply main and

water lowers (by steaming) until it reaches

normal level in boiler. Turn off oil burner.

Drain boiler. Open all radiator valves.

Reinstall all supply main air valves. Open

gate valve in Hartford Loop.

v. When boiler has cooled down sufficiently

(crown sheet of sections are not too hot to

touch), close the drain valves at boiler and

in return main and feed water slowly up to

normal level in boiler. Turn on oil burner

and allow boiler to steam for 10 minutes,

then turn off burner. Draw off one quart of

water from bottom gauge glass fitting and

discard. Draw off another quart sample and

if this sample is not clear, repeat the cycle

of draining the boiler and return main and

refilling the boiler until sample is clear.

vi. If the boiler water becomes dirty again

at a later date due to additional sediment

loosened up in the piping, close gate valve

in Hartford Loop, open drain valve in

return main, turn on oil burner and allow

Condensate to flow to drain until it has run

clear for at least 30 minutes while feeding

water to boiler so as to maintain normal

water level. Turn off oil burner, drain boiler,

open gate valve in Hartford Loop, then

repeat the full "Boiler and System Cleaning"

procedure outlined in Paragraph B starting

on Page 30.

e. Make pH or Alkalinity Test.
After boiler and system have been cleaned and

refilled as previously described, test the pH of

the water in the system. This can easily be done

by drawing a small sample of boiler water and

testing with hydrion paper which is used in the

same manner as litmus paper, except it gives

specific readings. A color chart on the side of the

small hydrion dispenser gives the reading in pH.

Hydrion paper is inexpensive and obtainable

from any chemical supply house or through your

local druggist. The pH should be higher than

7, but lower than 11. Add some of the washout

chemical (caustic soda), if necessary, to bring the

pH within the specified range.

f. Boiler is now ready to be put into service.

2. WATER BOILERS:

a. Filling of boiler and system.
GENERAL In a hot water heating system,

the boiler and entire system (other than the

expansion tank) must be full of water for

satisfactory operation. Water should be added

to the system until the boiler pressure gauge

registers 12 psi. To insure that the system is full,

NOTICE

Check with local authorities or consult local

water treatment services for acceptable chemical

cleaning compounds.

iii. Start burner and operate sufficiently to boil

the water without producing steam pressure.

Boil for about 5 hours. Open boiler feed

pipe sufficiently to permit a steady trickle

of water from the surface blow-off pipe.

Continue this slow boiling and trickle of

overflow for several hours until the water

coming from the overflow is clear.

iv. Stop burner and drain boiler in a manner

and to a location that hot water can be

discharged with safety.

v. Refill boiler to normal water line. If water

in gauge glass does not appear to be clear,

repeat steps (i. thru iii.) and boil out the

boiler for a longer time.

b. Low pressure steam boilers such as the CL

Series should be maintained with appropriate

water treatment compounds. Add suitable water

treatment compounds as recommended by your

qualified water treatment company.

c. Remove temporary surface blow-off piping, plug

tapping and reinstall safety valve. Boil or bring

water temperature to 180°F promptly in order to

drive off the dissolved gases in the fresh water.

d. If unsteady water line, foaming or priming

persist, install gate valve in Hartford Loop and

drain valves in return main and at boiler as

shown in Figure 9 and proceed as follows:

i Connect hoses from drain valves to floor

drain. Close gate valve in Hartford Loop and

open drain valve in return main. Fill boiler

to normal water level, turn on oil burner and

operate boiler at this water level for at least

30 minutes after the condensate begins to

run hot, then turn off burner.

Close all radiator valves. Remove all supply

main air valves and plug the openings in

supply main.

ii. Draw about 5 gallons of hot water from

boiler into a container and dissolve into it

the appropriate amount of a recommended

boilout compound. Remove safety valve

from boiler and pour this solution into

boiler, then reinstall safety valve.

iii. Turn on oil burner and keep operating while

feeding water to boiler slowly. This will

raise water level in boiler slowly so that

water will be boiling hot and will rise slowly

into supply main and back through return

main, flowing from drain hose at about

180°F. Continue until water runs clear from

drain hose for at least 30 minutes.

Advertising