Gas piping and pressures, Installing heater and louvers (cont’d), Installing louvers – Thomas & Betts LDAP 1200 User Manual

Page 10: Sizing gas supply line, Desired throw pattern

Advertising
background image

Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 10

Installing Louvers

NOTE: Do not install louvers
if installing a nozzle. Follow
the instructions shipped with
the nozzle.

Louver Installation Instructions:

1) With the wider section of the louver facing out of the heater, place one of the compres-

sion springs over the tab on the notched end of a louver. The end of the louver with the
spring will fit in any direction in the square opening. How the louver turns depends on
which end of the louver is inserted first.

2) Depending on the throw pattern selected, push the louver tab with the spring into a

hole in the discharge opening and insert the louver tab on the other end into the
corresponding hole on the opposite side.

3) Continue until all louvers are installed.

Adjust the louvers to provide the

desired throw pattern.

Airflow direction;

springs are on

the upper end.

Airflow direction;

springs are on

the lower end.

Wider side of the louver

blade must always be

facing out of the heater.

Compression Spring

FIGURE 6 - Use
Compression Springs to
Install Louvers in the
Discharge Opening(s)

CAUTION: To avoid getting
burned, adjust louvers while
heater is not operating. If
adjusting louvers while
heater is operating, wear
gloves.

After the unit is suspended/mounted, install the air directional louvers or optional
nozzle. If an optional nozzle is being installed, follow the instructions included with
the nozzle. If a nozzle is not being used, install the louvers in the discharge opening(s).
Louvers and springs are in the hardware kit shipped with the heater.
Before actually installing the louvers, note the louver curve and determine how the
louvers should be positioned to provide the optimal throw pattern. Opening is square
so louvers may be installed either horizontal or vertical. Louvers may be installed
with the curve all the same direction (either way) or the right half one way and left
the other as illustrated in FIGURE 6.

Airflow direction depends on
how the louvers are installed.

WARNING: This appliance is equipped for a maximum gas supply
pressure of 1/2 psi, 3.5 kPa, or 14 inches water column. Supply
pressure greater than 1/2 psi requires installation of an additional
lockup-type service regulator external to the heater.

WARNING: PRESSURE TESTING SUPPLY PIPING

Test Pressures Above 1/2 PSI: Disconnect the heater and manual valve from the
gas supply line which is to be tested. Cap or plug the supply line.
Test Pressures Below 1/2 PSI: Before testing, close the manual valve on the heater.

12. Gas Piping

and
Pressures

Sizing Gas Supply
Line

Capacity of Piping - Cubic Feet per Hour based on 0.3" w.c. Pressure Drop

Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)

Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)

Length

Diameter of Pipe

of 1"

1-1/4"

1-1/2"

2"

2-1/2"

Pipe

Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane

20'

350

214

730

445

1100

671

2100

1281

3300

2013

30'

285

174

590

360

890

543

1650

1007

2700

1647

40'

245

149

500

305

760

464

1450

885

2300

1403

50'

215

131

440

268

670

409

1270

775

2000

1220

60'

195

119

400

244

610

372

1105

674

1850

1129

70'

180

110

370

226

560

342

1050

641

1700

1037

80'

170

104

350

214

530

323

990

604

1600

976

90'

160

98

320

195

490

299

930

567

1500

915

100'

150

92

305

186

460

281

870

531

1400

854

125'

130

79

275

168

410

250

780

476

1250

763

150'

120

73

250

153

380

232

710

433

1130

689

175'

110

67

225

137

350

214

650

397

1050

641

200'

100

61

210

128

320

195

610

372

980

598

Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.

Refer to National Fuel Gas Code for additional information on line sizing.

WARNING: All com-
ponents of a gas supply
system must be leak
tested prior to placing
equipment in service.
NEVER TEST FOR
LEAKS WITH AN OPEN
FLAME. Failure to
comply could result in
personal injury, property
damage or death.