Thermostat and connections (cont’d), Factory wiring crimp terminal, Field wiring – Thomas & Betts LDAP 1200 User Manual

Page 16: Ldap 1200 thermostat wiring, Cl2 cl1 cl3, Cl18 cl7, Cl18, W2 r w1 g, W2 w1 r g, Y2 y1 c

Advertising
background image

Form RZ-NA-I-LDAP, P/N 207733 (Rev 2), Page 16

Multiple Heater
Control - Option
CL31 and Option
CL32

If the heater was ordered with a multiple heater control option, one thermostat can be used
to control multiple heaters. The option will control a maximum of six Size 400 heaters, a
maximum of three Size 800 heaters, or a maximum of two Size 1200 heaters.
The option includes a 40 VA transformer that replaces the standard transformer in the
”master” heater and a relay assembly that attaches to the “slave” heater. Option CL31
provides for control of two heaters. If control of additional heaters is desired, Option CL32
which is the relay assembly only must be added to each of the “slave” heaters.
The option packages are shipped separately and include complete instructions for installa-
tion and wiring.

W2

R

W1

G

W

(OPT CL1) W

.R. 1C30-341 THERMOST

A

T

R

R

(OPT CL2) W

.R. 1C30-341

W

-S23-6 SUBBASE

W

G

W2

R

W1

G

Q674G SUBBASE

(OPT CL7) T874F THERMOST

A

T

W2

R

W1

Q674C SUBBASE

(OPT CL18) T874F THERMOST

A

T

RH

W2

RC

W1

G

W2

W1

R

G

(OPT CL3) T874F THERMOST

A

T OR

R

W2

W1

G

W2

W1

R

G

W2

R

G

W1

NOTE 3

R

PR

PR

R

PR

R

PR

R

PR

R

PR

R

Y2

Y1

C

UNIT #1

TERMINAL STRIP

Y2

Y1

C

UNIT #1

TERMINAL STRIP

Y2

Y1

C

TERMINAL STRIP

UNIT #2

Y2

Y1

C

TERMINAL STRIP

UNIT #2

Y2

Y1

C

Y2

Y1

C

TERMINAL STRIP UNIT #3

UNIT #3

TERMINAL STRIP

TERMINAL STRIP

Q674G SUBBASE

(OPT CL7) T874F THERMOST

A

T

R

W2

Q674C SUBBASE

(OPT CL18) T874F THERMOST

A

T

W1

RH

RC

G

W2

W1

Y1

Y2

C

W2

R

W1

G

SINGLE STAGE HEATING

SINGLE STAGE HEATING

WITH RECIRCULATION

TWO STAGE HEATING

UNIT #1

R

PR

W2

C

R

R

W1

G

PR

W2

Y2

Y1

C

R

W1

R

G

PR

TERMINAL STRIP

UNIT #2

Y2

Y1

TERMINAL STRIP UNIT #3

FACTORY WIRING
CRIMP TERMINAL

LDAP 1200 THERMOSTAT WIRING

FIELD WIRING

WD# 189506 REV. #2

LDAP 1200 - Thermostat Option CL1,

CL2, CL3, CL7 or CL18

NOTES:

1) Set the anticipator at 0.6 amps.

2) For 400,000 BTUH low fire, do

not install this jumper.

3) For 800,000 BTUH low fire, do

not install this jumper.

4) Set thermostat first stage anticipator

at 0.6 amps and and second stage

anticipator at 0.2 amps.

5) Jumper thermostat terminals RH

to RC.

6) Jumper thermostat terminals RH

to RC and G to W1.

7) Set thermostat first stage anticipator at

maximum amps and second stage

anticipator at 0.6 amps.

(SEE NOTE #1)

CL2

CL1

CL3

(SEE NOTE #7)

CL18

CL7

(SEE NOTES #6 & #7)

(SEE NOTE #1)

CL18

CL7

(SEE

NOTE

#4

AND

#5)

(SEE NOTE #4)

NOTE 2

FIGURE 12 - Thermostat
Connections for Model
LDAP 1200 with Option
CL1, CL2, CL3, CL7, or
CL18

15. Thermostat and Connections (cont’d)

Advertising