TOA Electronics SSDVT-4035CNM User Manual

Page 18

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

18

H1

V

V1

H

V

H1

H

V1

Ceiling

Firestop / Spacer
(SV4.5VF)

Ceiling

Firestop / Spacer
(SV4.5VF)

Wall Firestop/

Spacer (SV4.5HF)

Wall Firestop/

Spacer (SV4.5HF)

Ceiling

Firestop / Spacer
(SV4.5VF)

Example: If 20 feet total (H+H

1

)

horizontal vent run is needed,
then 4 feet minimum of (V) verti-
cal vent will be required.

This table shows a 1(V) to 5(H)
ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet
of (H+H

1

) horizontal run up to

a maximum total horizontal run
of 20 feet.

An elbow is acceptable as 1 foot
of vertical rise except where
an elbow is the only vertical
component in the system. See
Figure 35.

Table D

H +

H

1

Maximum

V Minimum

feet

(meter)

feet

(meter)

5

(1.524)

Elbow Only

5

(1.524)

1

(0.305)

10

(3.048)

2

(0.610)

15

(4.572)

3

(0.914)

20

(6.096)

4

(1.219)

H + H

1

= 20 feet (6.096 m) Max.

V + V

1

+ H + H

1

= 40 ft. (12.192 m) Max.

Table C

H

+H

1

Maximum

H

Maximum

V Minimum

feet

(meter)

feet

(meter)

feet

(meter)

5

(1.524)

2

(0.610)

1

(0.305)

10

(3.048)

4

(1.219)

2

(0.610)

15

(4.572)

6

(1.829)

3

(0.914)

20

(6.096)

8

(2.438)

4

(1.219)

V + V1 + H + H1 = 40 feet (12.2 m) Max

H = 8 feet (2.438 meters) Max.

H + H1 = 20 feet (6.096 meters) Max.

Example: If 20 feet total (H+H

1

) horizontal vent run is needed,

then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H+H

1

) horizontal run up to a

maximum total horizontal run of 20 feet.

When using Secure Flex, use Firestop / Spacer SF4.5VF

When using Secure Flex, use Firestop / Spacer SF4.5HF

When using Secure Flex, use Firestop / Spacer SF4.5VF

When using Secure Flex, use Firestop / Spacer SF4.5HF

Figure 29 - Rear Vent - THREE ELBOWS

Figure 30 - Top Vent - THREE ELBOWS

VERTICAL VENT FIGURES/TABLES

(CONTINUED)

HORIZONTAL (OUTSIDE WALL)
TERMINATION SYSTEM

Figure 31, and Figures 34 to 40 on Pages
21 to 23
and their associated Horizontal Vent
Table illustrate the various horizontal venting
confi gurations that are possible for use with
these appliances. Secure Vent pipe applications
are shown in these Figures; Secure Flex pipe
may also be used. A Horizontal Vent Table sum-
marizes each system’s minimum and maximum
vertical and horizontal length values that can be
used to design and install the vent components
in a variety of applications.

Both of these horizontal vent systems terminate
through an outside wall. Building Codes limit or
prohibit terminating in specifi c areas. Refer to
Figure 7 on Page 8 for location guidelines.

Secure Vent SV4.5 direct vent system compo-
nents are unitized concentric pipe components
featuring positive twist lock connection, (refer
to Figure 20
on Page 15). All of the appli-
ances covered in this document are fi tted with
collars having locking inclined channels. The
dimpled end of the vent components fi t over
the appliance collar to create the positive twist
lock connection.

A. Plan the vent run -
Analyze the vent routing and determine the
types and quantities of sections required

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2"
(572 mm), 34-1/2" (876 mm) and 46-1/2"
(1181 mm) net section lengths are available.
Plan the vent lengths so that a joint does not
occur at the intersection of ceiling or roof joists.
Make allowances for elbows as indicated in
Figure 22.

Maintain a minimum 1" (25 mm) clearance to
combustibles on the vertical sections. Clear-
ances for the horizontal runs are; 3" (76 mm)
on top, 1" (25 mm) on sides, and 1" (25 mm)
at the bottom.

Advertising