Warning, Never use an open fl ame to check for leaks – TOA Electronics SSDVT-4035CNM User Manual

Page 27

Advertising
background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

27

Replace logs if removed for pilot inspection.

To light the burner; turn “ON” the remote wall
switch and rotate the gas valve control knob
counterclockwise to the “ON” position.

Figure 50

Proper Pilot Flame Appearance

Thermocouple

Thermopile

Pilot
Nozzels

1/8" Min.

(3 mm)

Igniter Rod

Hood

HONEYWELL MILLIVOLT PILOT ASSEMBLY

Figure 49

Thermocouple

Thermopile

Pilot
Nozzels

SIT MILLIVOLT PILOT ASSEMBLY

3/8" Min.

(9 mm)

Igniter Rod

Hood

Proper Pilot Flame Appearance

3/8" Min.

(9 mm)

TEST ALL CONNECTIONS FOR GAS LEAKS
(FACTORY AND FIELD):

WARNING

Never use an open fl ame to
check for leaks.

Turn on gas supply and test for gas leaks using a
gas leak test solution (also referred to as bubble
leak solution). Note: Using a soapy water solution
(50% dish soap, 50% water) is an effective leak
test solution but it is not recommended, because
the soap residue that is left on the pipes/fi ttings
can result in corrosion over time.

A. Light the appliance (refer to the lighting

instructions label in control compartment or
homeowner's manual).

B. Brush all joints and connections with the gas

leak test solution to check for leaks. If bubbles
are formed, or gas odor is detected, turn the
gas control knob (off/pilot/on) to the “OFF”
position. Either tighten or refasten the leaking
connection, then retest as described above.

C. When the gas lines are tested and leak free be

sure to rinse off the leak testing solution,

D. Turn on burner then observe the individual

tongues of fl ame on the burner. Make sure
all ports are open and producing fl ame evenly
across the burner. If any ports are blocked, or
partially blocked, clean out the ports.

CONTROL COMPARTMENT ACCESS /
LOUVER PANEL INSTRUCTIONS
(

Ref. Figure 47

)

NOTE: The top louvered panel and the bottom
louvered control panel door remove and install
the same way as follows:

The gas controls can be found behind the control
compartment access door.

Removing Control Compartment Door:
Open the door by gently lifting it upward until the
hook catches on boths sides clear the locating
slots. Then pull door out to remove.

On millivolt systems, the piezo igniter, HI/LO
fl ame adjustment knob, and pilot and main
gas OFF/ON control knob are located below
the glass panel enclosure. The gas valve for
electronic systems is also located below the
glass enclosure panel. See Figure 47.

Reinstalling Control Compartment Door:
To reinstall, insert the hook catches on each
side of the door into the corresponding slots
in the control compartment opening, then
gently push forward and slide down until it
locks in place.

Figure 48

Sit and Honeywell Millivolt Gas Valve

Showing Piezo Igniter Location (Each Unit is

Equipped with Only One of these Gas Valves)

Piezo

Igniter

SIT Gas Valve

Honeywell
Gas Valve

Step 7. CHECKING APPLIANCE OPERA-
TION

With the gas line installed, run initial system
checkout before closing up the front of the
appliance. Follow the pilot lighting instructions
provided in the Homeowner's Care and Opera-
tion Instructions. For piezo igniter location see
Figure 48
(millivolt appliances only).

Note: The (pull-out) Lighting instructions label
can be found in the control compartment
(see Figure 47).

When fi rst lighting the appliance, it will take
a few minutes for the line to purge itself of
air. Once purging is complete, the pilot and
burner will light and operate as indicated in
the instruction manual. Subsequent lightings
of the appliance will not require such purging.
Inspect the pilot fl ame.

SIT and Honeywell Millivolt Appliance
Checkout

The pilot fl ame should be steady, not lifting
or fl oating. Flame should be blue in color with
traces of orange at the outer edge.

The top 3/8" (10 mm) at the pilot generator
(thermopile) and the top 1/8" min (tip) of the
quick drop out thermocouple should be engulfed
in the pilot fl ame. The fl ame should project 1" (25
mm) beyond the hood at all three ports (Figure
49 - SIT, Figure 50 - Honeywell
).

To light the burner; rotate the gas valve control
knob counterclockwise to the “ON” position
then turn “ON” the OFF/ON switch (installed
at Step 4).

Figure 47

OPENING CONTROL
COMPARTMENT DOOR

Control Valve

Lower Control
Compartment Door

Lift the Lower Control
Compartment Door
up and pull out to
remove.

Up

Out

Hook Catch

Observe the individual tongues of fl ame on
the burner. Make sure all ports are open and
producing fl ame evenly across the burner. If
any ports are blocked, or partially blocked,
clean out the ports.

Advertising