Performance data — 60 hz (20–25ton) full load, Performance data — 60 hz, 20–25 ton) full load – Trane CG-PRC007-EN User Manual

Page 22

Advertising
background image

CG-PRC007-EN

22

Performance
Data — 60 HZ

Table PD-3 — 20 Ton — CGAF-C20

Entering Condenser Air Temperature (Degree F)

75.0

85.0

95.0

105.0

115.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

20

28

12.0

15.6

9.2

11.4

17.3

8.0

10.8

19.2

6.8

10.1

21.3

5.7

9.4

23.8

4.8

25

24

13.4

16.0

10.0

12.7

17.7

8.6

12.1

19.6

7.4

11.3

21.8

6.2

10.6

24.3

5.2

30

19

14.8

16.4

10.8

14.1

18.1

9.4

13.4

20.1

8.0

12.6

22.3

6.8

11.8

24.9

5.7

35

14

16.4

16.9

11.6

15.6

18.6

10.1

14.8

20.6

8.6

14.0

22.9

7.3

13.1

25.4

6.2

40

0

18.1

17.4

12.5

17.3

19.2

10.9

16.4

21.2

9.3

15.5

23.5

7.9

14.5

26.1

6.7

42

0

18.8

17.6

12.8

18.0

19.4

11.1

17.0

21.4

9.6

16.1

23.7

8.1

15.1

26.3

6.9

44

0

19.5

17.8

13.2

18.6

19.6

11.4

17.7

21.6

9.8

16.7

24.0

8.3

15.6

26.5

7.1

45

0

19.8

17.9

13.3

18.9

19.7

11.5

18.0

21.7

9.9

17.0

24.1

8.5

15.9

26.7

7.1

46

0

20.1

18.0

13.5

19.2

19.8

11.7

18.3

21.8

10.0

17.3

24.2

8.6

16.2

26.8

7.2

48

0

20.8

18.2

13.8

19.9

20.0

11.9

18.9

22.1

10.3

17.9

24.4

8.8

16.7

27.0

7.4

50

0

21.5

18.4

14.1

20.6

20.2

12.2

19.5

22.3

10.5

18.5

24.7

9.0

17.3

27.3

7.6

55

0

23.3

18.9

14.8

22.3

20.8

12.9

21.2

22.9

11.1

20.0

25.3

9.5

18.8

27.9

8.1

60

0

25.2

19.4

15.5

24.0

21.4

13.5

22.9

23.5

11.7

21.6

26.0

10.0

20.3

28.6

8.5

Table PD-4 — 25 Ton — CGAF-C25

Entering Condenser Air Temperature (Degree F)

75.0

85.0

95.0

105.0

115.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

20

28

15.6

20.9

8.9

14.8

22.9

7.8

14.0

25.2

6.7

13.2

27.8

5.7

12.3

30.7

4.8

25

24

17.4

21.4

9.7

16.5

23.4

8.5

15.7

25.8

7.3

14.7

28.4

6.2

13.8

31.4

5.3

30

19

19.3

21.9

10.6

18.4

24.0

9.2

17.4

26.4

7.9

16.4

29.1

6.8

15.4

32.1

5.8

35

14

21.3

22.5

11.4

20.4

24.6

9.9

19.3

27.0

8.6

18.2

29.8

7.4

17.1

32.8

6.3

40

0

23.7

23.1

12.3

22.6

25.3

10.7

21.5

27.8

9.3

20.3

30.6

8.0

19.1

33.7

6.8

42

0

24.6

23.3

12.6

23.5

25.5

11.0

22.3

28.0

9.5

21.1

30.8

8.2

19.8

34.0

7.0

44

0

25.4

23.6

13.0

24.3

25.8

11.3

23.1

28.3

9.8

21.9

31.1

8.4

20.6

34.3

7.2

45

0

25.9

23.7

13.1

24.7

25.9

11.5

23.5

28.4

9.9

22.3

31.3

8.5

21.0

34.4

7.3

46

0

26.3

23.8

13.3

25.2

26.0

11.6

23.9

28.6

10.0

22.7

31.4

8.7

21.3

34.6

7.4

48

0

27.3

24.1

13.6

26.0

26.3

11.9

24.8

28.9

10.3

23.5

31.7

8.9

22.1

34.9

7.6

50

0

28.2

24.3

13.9

26.9

26.6

12.2

25.6

29.2

10.6

24.3

32.0

9.1

22.9

35.2

7.8

55

0

30.6

25.0

14.7

29.2

27.3

12.9

27.8

29.9

11.2

26.4

32.8

9.6

24.9

36.1

8.3

60

0

33.0

25.6

15.5

31.6

28.0

13.5

30.1

30.7

11.8

28.6

33.7

10.2

27.0

36.9

8.8

Notes:
1. Data based on 0.0001 fouling factor at sea level.
2. Interpolation between points is permissible.
3. Extrapolation beyond points is not permissible.
4. EER - Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors,

condenser fans and control power.

5. Ratings based on evaporator drop of 10°F.
6. Rated in accordance with ARI Standard 550/590-98.
7. Minimum recommended ethylene glycol percentage used for leaving water temperatures below 40°F.
8. Use the following equation to calculate COP values at other than ARI conditions, COP = EER x .2928.

(20–25 Ton)
Full Load

Advertising