CG-PRC007-EN

26

Entering Condenser Air Temperature (Degree F)

85.0

95.0

105.0

115.0

120.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

40

0

28.8

30.0

11.5

27.3

33.5

9.8

25.7

37.6

8.2

24.0

42.2

6.8

23.1

44.6

6.2

42

0

29.8

30.2

11.8

28.3

33.8

10.0

26.7

37.9

8.4

25.0

42.5

7.0

24.1

45.0

6.4

44

0

30.9

30.5

12.2

29.3

34.1

10.3

27.7

38.2

8.7

25.9

42.8

7.3

25.0

45.3

6.6

45

0

31.5

30.6

12.3

29.9

34.3

10.5

28.2

38.4

8.8

26.4

43.0

7.4

25.4

45.5

6.7

46

0

32.0

30.8

12.5

30.4

34.4

10.6

28.7

38.5

8.9

26.9

43.2

7.5

25.9

45.7

6.8

48

0

33.1

31.1

12.8

31.5

34.7

10.9

29.7

38.9

9.2

27.8

43.5

7.7

26.9

46.1

7.0

50

0

34.3

31.3

13.1

32.6

35.0

11.2

30.8

39.2

9.4

28.8

43.9

7.9

27.8

46.4

7.2

Table PD-15 — 40 Ton — CGAF-C40

Entering Condenser Air Temperature (Degree F)

85.0

95.0

105.0

115.0

120.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F) Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

40

0

36.0

37.2

11.6

34.2

41.3

9.9

32.3

45.9

8.4

30.2

51.0

7.1

29.1

53.8

6.5

42

0

37.3

37.5

11.9

35.5

41.6

10.2

33.5

46.2

8.7

31.4

51.4

7.3

30.2

54.2

6.7

44

0

38.7

37.8

12.3

36.8

41.9

10.5

34.8

46.6

9.0

32.6

51.8

7.5

31.4

54.6

6.9

45

0

39.4

38.0

12.4

37.5

42.1

10.7

35.4

46.8

9.1

33.2

52.0

7.7

32.0

54.8

7.0

46

0

40.1

38.2

12.6

38.1

42.3

10.8

36.0

47.0

9.2

33.8

52.2

7.8

32.6

55.0

7.1

48

0

41.5

38.5

12.9

39.5

42.7

11.1

37.3

47.4

9.5

35.0

52.6

8.0

33.8

55.4

7.3

50

0

42.9

38.8

13.3

40.9

43.0

11.4

38.7

47.7

9.7

36.3

53.0

8.2

35.1

55.9

7.5

Table PD-16 — 50 Ton — CGAF-C50

Entering Condenser Air Temperature (Degree F)

85.0

95.0

105.0

115.0

120.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

40

0

46.6

48.3

11.6

44.1

53.7

9.9

41.5

59.8

8.3

38.8

66.6

7.0

37.3

70.3

6.4

42

0

48.3

48.7

11.9

45.8

54.2

10.1

43.1

60.3

8.6

40.2

67.2

7.2

38.7

70.9

6.6

44

0

50.0

49.2

12.2

47.5

54.7

10.4

44.7

60.9

8.8

41.8

67.8

7.4

40.2

71.5

6.8

45

0

50.9

49.4

12.4

48.3

55.0

10.5

45.5

61.2

8.9

42.5

68.1

7.5

41.0

71.8

6.8

46

0

51.8

49.7

12.5

49.2

55.2

10.7

46.3

61.5

9.0

43.3

68.4

7.6

41.7

72.1

6.9

48

0

53.6

50.2

12.8

50.9

55.8

10.9

48.0

62.1

9.3

44.9

69.0

7.8

43.2

72.8

7.1

50

0

55.4

50.7

13.1

52.6

56.3

11.2

49.6

62.7

9.5

46.4

69.7

8.0

44.8

73.4

7.3

Table PD-17— 60 Ton — CGAF-C60

Performance
Data — 50 HZ

(40–60 Ton)
Full Load

Notes:
1. Data based on 0.0001 fouling factor at sea level.
2. Interpolation between points is permissible.
3. Extrapolation beyond points is not permissible.
4. EER - Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.
5. Ratings based on evaporator drop of 10°F.
6. Rated in accordance with ARI Standard 550/590-98
7. Minimum recommended ethylene glycol percentage used for leaving water temperatures below 40°.
8. Data obtained assuming 400 Volt Supply.
9. Use the following equation to calculate COP values at other than ARI conditions, COP = EER x .2928.