Data — 60 HZ

(30–40 Ton)
Full Load

Entering Condenser Air Temperature (Degree F)

75.0

85.0

95.0

105.0

115.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

20

28

18.8

25.7

8.8

17.9

28.1

7.6

16.9

30.9

6.6

15.9

34.0

5.6

14.9

37.6

4.7

25

24

21.0

26.3

9.6

20.0

28.7

8.4

18.9

31.5

7.2

17.8

34.8

6.2

16.7

38.4

5.2

30

19

23.3

26.8

10.4

22.2

29.3

9.1

21.1

32.2

7.9

19.9

35.5

6.7

18.7

39.2

5.7

35

14

25.8

27.4

11.3

24.6

29.9

9.9

23.4

32.9

8.5

22.1

36.2

7.3

20.8

40.0

6.2

40

0

28.7

28.0

12.3

27.4

30.7

10.7

26.1

33.7

9.3

24.7

37.1

8.0

23.2

40.9

6.8

42

0

29.7

28.3

12.6

28.4

30.9

11.0

27.0

34.0

9.5

25.6

37.4

8.2

24.1

41.3

7.0

44

0

30.8

28.5

13.0

29.5

31.2

11.3

28.0

34.3

9.8

26.6

37.7

8.4

25.0

41.6

7.2

45

0

31.4

28.6

13.1

30.0

31.3

11.5

28.5

34.4

9.9

27.0

37.9

8.6

25.5

41.8

7.3

46

0

31.9

28.8

13.3

30.5

31.5

11.6

29.0

34.6

10.1

27.5

38.1

8.7

26.0

41.9

7.4

48

0

33.0

29.0

13.6

31.6

31.8

11.9

30.1

34.9

10.3

28.5

38.4

8.9

26.9

42.3

7.6

50

0

34.1

29.3

14.0

32.7

32.0

12.2

31.1

35.2

10.6

29.5

38.7

9.1

27.9

42.6

7.8

55

0

37.0

29.9

14.8

35.5

32.8

13.0

33.8

36.0

11.3

32.1

39.6

9.7

30.3

43.5

8.4

60

0

40.1

30.6

15.7

38.4

33.5

13.7

36.6

36.8

11.9

34.8

40.4

10.3

32.9

44.5

8.9

Table PD-5— 30 Ton — CGAF-C30

Table PD-6 — 40 Ton — CGAF-C40

Entering Condenser Air Temperature (Degree F)

75.0

85.0

95.0

105.0

115.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

20

28

23.0

30.9

8.9

21.9

34.1

7.7

20.7

37.9

6.6

19.5

42.3

5.5

18.1

47.2

4.6

25

24

25.7

31.7

9.7

24.5

35.0

8.4

23.2

38.8

7.2

21.8

43.2

6.1

20.3

48.2

5.1

30

19

28.6

32.5

10.6

27.3

35.8

9.2

25.9

39.7

7.8

24.4

44.2

6.6

22.8

49.2

5.5

35

14

31.8

33.3

11.4

30.3

36.7

9.9

28.8

40.7

8.5

27.1

45.2

7.2

25.3

50.3

6.0

40

0

35.4

34.3

12.4

33.8

37.8

10.7

32.1

41.9

9.2

30.2

46.4

7.8

28.3

51.6

6.6

42

0

36.7

34.7

12.7

35.0

38.2

11.0

33.3

42.3

9.4

31.4

46.9

8.0

29.4

52.0

6.8

44

0

38.0

35.0

13.0

36.3

38.6

11.3

34.5

42.7

9.7

32.5

47.3

8.2

30.5

52.5

7.0

45

0

38.7

35.2

13.2

36.9

38.8

11.4

35.1

42.9

9.8

33.1

47.5

8.4

31.0

52.7

7.1

46

0

39.3

35.4

13.3

37.6

39.0

11.6

35.7

43.1

9.9

33.7

47.8

8.5

31.6

53.0

7.2

48

0

40.7

35.8

13.7

38.9

39.4

11.8

36.9

43.5

10.2

34.9

48.2

8.7

32.7

53.4

7.3

50

0

42.1

36.2

14.0

40.2

39.8

12.1

38.2

44.0

10.4

36.1

48.7

8.9

33.9

53.9

7.5

55

0

45.6

37.2

14.7

43.6

40.9

12.8

41.5

45.1

11.0

39.2

49.9

9.4

36.8

55.2

8.0

60

0

49.3

38.2

15.5

47.1

42.0

13.5

44.8

46.3

11.6

42.4

51.1

10.0

39.8

56.5

8.5

Notes:
1. Data based on 0.0001 fouling factor at sea level.
2. Interpolation between points is permissible.
3. Extrapolation beyond points is not permissible.
4. EER - Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, water temperatures below 40°F.
5. Ratings based on evaporator drop of 10°F condenser fans and control power
6. Rated in accordance with ARI Standard 550/590-98.
7. Minimum recommended ethylene glycol percentage used for leaving water temperatures below 40°F.
8. Use the following equation to calculate COP values at other than ARI conditions, COP = EER x .2928.

Advertising