Performance data — 50 hz (10–30ton) full load – Trane CG-PRC007-EN User Manual

Page 25

Advertising
background image

25

CG-PRC007-EN

Performance
Data — 50 HZ

(10–30 Ton)
Full Load

Entering Condenser Air Temperature (Degree F)

85.0

95.0

105.0

115.0

120.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

40

0

7.2

7.6

11.4

6.8

8.4

9.7

6.4

9.4

8.2

6.0

10.5

6.9

5.8

11.1

6.3

42

0

7.4

7.6

11.7

7.1

8.5

10.0

6.7

9.5

8.4

6.3

10.6

7.1

6.1

11.2

6.5

44

0

7.7

7.7

12.0

7.3

8.6

10.2

6.9

9.6

8.7

6.5

10.7

7.3

6.3

11.3

6.7

45

0

7.9

7.8

12.1

7.5

8.7

10.3

7.1

9.7

8.8

6.6

10.8

7.4

6.4

11.4

6.8

46

0

8.0

7.9

12.2

7.6

8.7

10.5

7.2

9.7

8.9

6.8

10.8

7.5

6.6

11.4

6.9

48

0

8.3

8.0

12.5

7.9

8.8

10.7

7.5

9.8

9.1

7.0

10.9

7.7

6.8

11.5

7.1

50

0

8.6

8.1

12.8

8.2

9.0

11.0

7.7

10.0

9.3

7.3

11.1

7.9

7.1

11.7

7.3

Table PD-10— 10 Ton — CGA 120

Table PD-11— 15 Ton — CGA 180

Entering Condenser Air Temperature (Degree F)

85.0

95.0

105.0

115.0

120.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

40

0

11.2

12.1

11.1

10.6

13.8

9.2

10.0

15.7

7.6

9.3

17.8

6.2

8.9

19.0

5.6

42

0

11.6

12.2

11.4

11.0

13.9

9.5

10.3

15.8

7.9

9.6

17.9

6.4

9.3

19.1

5.8

44

0

12.0

12.4

11.7

11.4

14.0

9.8

10.7

15.9

8.1

10.0

18.1

6.6

9.7

19.3

6.0

45

0

12.2

12.4

11.8

11.6

14.1

9.9

10.9

16.0

8.2

10.2

18.2

6.8

9.9

19.4

6.1

46

0

12.5

12.5

12.0

11.8

14.1

10.1

11.2

16.1

8.3

10.4

18.2

6.9

10.1

19.4

6.2

48

0

12.9

12.6

12.3

12.3

14.3

10.3

11.6

16.2

8.6

10.8

18.4

7.1

10.5

19.6

6.4

50

0

13.4

12.7

12.6

12.7

14.4

10.6

12.0

16.3

8.8

11.2

18.5

7.3

10.9

19.7

6.6

Entering Condenser Air Temperature (Degree F)

85.0

95.0

105.0

115.0

120.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

40

0

14.7

15.2

11.7

14.0

17.0

9.9

13.2

19.0

8.3

12.3

21.3

6.9

11.9

22.5

6.3

42

0

15.3

15.3

12.0

14.5

17.1

10.2

13.7

19.2

8.6

12.8

21.5

7.1

12.3

22.7

6.5

44

0

15.8

15.5

12.3

15.0

17.3

10.4

14.2

19.3

8.8

13.2

21.6

7.3

12.8

22.9

6.7

45

0

16.1

15.5

12.4

15.3

17.3

10.6

14.4

19.4

8.9

13.5

21.7

7.4

13.0

23.0

6.8

46

0

16.4

15.6

12.6

15.5

17.4

10.7

14.7

19.5

9.0

13.7

21.8

7.5

13.2

23.1

6.9

48

0

16.9

15.7

12.9

16.1

17.6

11.0

15.2

19.7

9.3

14.2

22.0

7.8

13.7

23.3

7.1

50

0

17.5

15.9

13.2

16.6

17.8

11.2

15.7

19.9

9.5

14.7

22.2

8.0

14.2

23.5

7.3

Table PD-12 — 20 Ton — CGAF-C20

Entering Condenser Air Temperature (Degree F)

85.0

95.0

105.0

115.0

120.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

40

0

19.3

19.8

11.7

18.3

21.9

10.0

17.3

24.3

8.5

16.2

27.0

7.2

15.6

28.5

6.6

42

0

20.0

20.0

12.0

19.0

22.1

10.3

17.9

24.5

8.8

16.8

27.3

7.4

16.2

28.7

6.8

44

0

20.7

20.1

12.3

19.7

22.3

10.6

18.6

24.8

9.0

17.4

27.5

7.6

16.8

29.0

7.0

45

0

21.1

20.2

12.5

20.1

22.4

10.7

18.9

24.9

9.1

17.7

27.6

7.7

17.1

29.1

7.1

46

0

21.5

20.3

12.7

20.4

22.5

10.9

19.3

25.0

9.3

18.1

27.7

7.8

17.4

29.2

7.2

48

0

22.2

20.5

13.0

21.1

22.7

11.2

20.0

25.2

9.5

18.7

28.0

8.0

18.1

29.4

7.4

50

0

23.0

20.7

13.3

21.9

22.9

11.4

20.7

25.4

9.8

19.4

28.2

8.3

18.7

29.7

7.6

Table PD-13 — 25 Ton — CGAF-C25

6. Rated in accordance with ARI Standard 550/590-98
7. Minimum recommended ethylene glycol percentage used for leaving

water temperatures below 40°.

8. Data obtained assuming 400 Volt Supply.
9. Use the following equation to calculate COP values at other

than ARI conditions, COP = EER x .2928.

Entering Condenser Air Temperature (Degree F)

85.0

95.0

105.0

115.0

120.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

40

0

23.4

23.9

11.7

22.2

26.5

10.1

21.0

29.5

8.6

19.7

32.8

7.2

19.0

34.6

6.6

42

0

24.2

24.1

12.1

23.1

26.7

10.4

21.8

29.7

8.8

20.5

33.0

7.4

19.7

34.8

6.8

44

0

25.1

24.3

12.4

23.9

27.0

10.6

22.6

29.9

9.1

21.2

33.3

7.7

20.5

35.1

7.0

45

0

25.6

24.4

12.6

24.3

27.1

10.8

23.0

30.1

9.2

21.6

33.4

7.8

20.9

35.2

7.1

46

0

26.0

24.5

12.7

24.8

27.2

10.9

23.4

30.2

9.3

22.0

33.5

7.9

21.3

35.3

7.2

48

0

26.9

24.7

13.1

25.7

27.4

11.2

24.3

30.4

9.6

22.8

33.8

8.1

22.0

35.6

7.4

50

0

27.9

24.9

13.4

26.5

27.6

11.5

25.1

30.7

9.8

23.6

34.0

8.3

22.8

35.9

7.6

Table PD-14 — 30 Ton — CGAF-C30

Notes:
1. Data based on 0.0001 fouling factor at sea level.
2. Interpolation between points is permissible.
3. Extrapolation beyond points is not permissible.
4. EER - Energy Efficiency Ratio (Btu/watt-hour). Power

inputs include compressors, condenser fans and control power.

5. Ratings based on evaporator drop of 10°F.