29

CG-PRC007-EN

Percent

Entering Condenser Air Temperature (Degrees F)

Load

75

85

95

105

115

120

Percent

Entering Condenser Air Temperature (Degrees F)

Load

75

85

95

105

115

120

EER

14.1

12.2

10.4

8.8

7.4

6.7

100

Capacity

52.2

49.8

47.3

44.5

41.6

40.1

System KW

44.4

49.2

54.6

60.8

67.7

71.4

EER

14.9

12.9

11.0

9.4

7.9

7.2

75

Capacity

40.5

38.7

36.7

34.6

32.4

31.2

System KW

32.7

36.1

40.0

44.4

49.3

52.0

EER

16.2

14.2

12.3

10.5

8.9

8.2

50

Capacity

28.6

27.4

26.1

24.7

23.3

22.5

System KW

21.2

23.2

25.5

28.2

31.2

32.9

EER

15.5

13.4

11.5

9.8

8.2

7.5

25

Capacity

13.8

13.2

12.5

11.8

11.1

10.7

System KW

10.6

11.8

13.0

14.5

16.1

17.0

Percent

Entering Condenser Air Temperature (Degrees F)

Load

75

85

95

105

115

120

EER

14.2

12.3

10.5

9.0

7.5

6.9

100

Capacity

40.4

38.7

36.8

34.8

32.6

31.4

System KW

34.3

37.8

41.9

46.6

51.8

54.6

EER

14.7

12.8

11.0

9.4

7.9

7.3

80

Capacity

33.4

31.9

30.4

28.7

26.9

26.0

System KW

27.3

30.0

33.1

36.7

40.7

42.9

EER

15.5

13.6

11.8

10.1

8.6

7.9

60

Capacity

26.2

25.1

24.0

22.7

21.4

20.7

System KW

20.2

22.1

24.3

26.9

29.7

31.3

EER

14.5

12.6

10.8

9.2

7.7

7.1

30

Capacity

12.4

11.9

11.3

10.7

10.0

9.6

System KW

10.3

11.3

12.6

14.0

15.5

16.4

Notes:
1. Data based on 0.0001 fouling factor at sea level.
2. Interpolation between points is permissible.
3. Extrapolation beyond points is not permissible.
4. EER - Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors,

condenser fans and control power

5. Ratings based on evaporator drop of 10°F
6. Rated in accordance with ARI Standard 550/590-98.
7. Data obtained assuming 400 Volt supply.

EER

14.2

12.2

10.3

8.7

7.3

6.6

100

Capacity

32.4

30.9

29.3

27.7

25.9

25.0

System KW

27.4

30.5

34.1

38.2

42.8

45.3

EER

14.9

12.8

10.9

9.2

7.7

7.1

75

Capacity

25.2

24.0

22.8

21.5

20.2

19.5

System KW

20.3

22.5

25.0

27.9

31.3

33.1

EER

16.3

14.2

12.2

10.4

8.8

8.1

50

Capacity

17.8

17.1

16.3

15.4

14.5

14.0

System KW

13.2

14.5

16.0

17.7

19.8

20.9

EER

14.3

12.2

10.3

8.6

7.2

6.5

25

Capacity

8.4

8.0

7.6

7.1

6.7

6.4

System KW

7.1

7.9

8.9

9.9

11.1

11.8

(40–60 Ton)
Part Load

Performance
Data — 50 HZ

Table PD-24— 40 Ton — CGAF-C40

Table PD-25— 50 Ton — CGAF-C50

Table PD-26— 60 Ton — CGAF-C60