Performance data — 60 hz (50–60ton) full load, Performance data — 60 hz, 50–60 ton) full load – Trane CG-PRC007-EN User Manual

Page 24

Advertising
background image

CG-PRC007-EN

24

Performance
Data — 60 HZ

Entering Condenser Air Temperature (Degree F)

75.0

85.0

95.0

105.0

115.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

20

28

37.2

50.1

8.9

35.3

55.0

7.7

33.4

60.7

6.6

31.3

67.2

5.6

29.2

74.6

4.7

25

24

41.6

51.3

9.7

39.6

56.4

8.4

37.4

62.2

7.2

35.2

68.8

6.1

32.9

76.3

5.2

30

19

46.4

52.6

10.6

44.1

57.8

9.2

41.8

63.8

7.9

39.4

70.6

6.7

36.8

78.2

5.7

35

14

51.4

54.0

11.4

48.9

59.3

9.9

46.4

65.4

8.5

43.7

72.3

7.3

41.0

80.1

6.1

40

0

57.2

55.6

12.3

54.5

61.1

10.7

51.7

67.3

9.2

48.8

74.4

7.9

45.8

82.2

6.7

42

0

59.2

56.2

12.7

56.5

61.7

11.0

53.6

68.0

9.5

50.6

75.1

8.1

47.5

83.0

6.9

44

0

61.4

56.8

13.0

58.5

62.3

11.3

55.6

68.7

9.7

52.5

75.9

8.3

49.3

83.8

7.1

45

0

62.5

57.1

13.1

59.6

62.7

11.4

56.6

69.1

9.8

53.4

76.2

8.4

50.2

84.2

7.2

46

0

63.6

57.4

13.3

60.6

63.0

11.5

57.6

69.4

9.9

54.4

76.6

8.5

51.1

84.6

7.2

48

0

65.8

58.0

13.6

62.7

63.7

11.8

59.6

70.2

10.2

56.3

77.4

8.7

52.9

85.4

7.4

50

0

68.0

58.6

13.9

64.9

64.4

12.1

61.7

70.9

10.4

58.3

78.2

8.9

54.8

86.3

7.6

55

0

73.8

60.3

14.7

70.4

66.1

12.8

66.9

72.8

11.0

63.3

80.2

9.5

59.6

88.4

8.1

60

0

79.7

62.0

15.4

76.1

68.0

13.4

72.4

74.8

11.6

68.5

82.4

10.0

64.5

90.7

8.5

Entering Condenser Air Temperature (Degree F)

75.0

85.0

95.0

105.0

115.0

LWT

Percent Capacity System

Capacity System

Capacity

System

Capacity

System

Capacity System

(Deg F)

Glycol

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

20

28

28.5

39.7

8.6

27.1

43.4

7.5

25.6

47.7

6.4

24.1

52.6

5.5

22.5

58.2

4.6

25

24

31.9

40.5

9.4

30.4

44.3

8.2

28.7

48.7

7.1

27.1

53.8

6.0

25.3

59.5

5.1

30

19

35.6

41.4

10.3

33.9

45.3

9.0

32.1

49.8

7.7

30.3

55.0

6.6

28.4

60.7

5.6

35

14

39.5

42.4

11.2

37.7

46.4

9.7

35.8

51.0

8.4

33.8

56.2

7.2

31.7

62.0

6.1

40

0

44.1

43.5

12.2

42.1

47.6

10.6

40.0

52.3

9.2

37.8

57.6

7.9

35.5

63.5

6.7

42

0

45.7

43.9

12.5

43.6

48.0

10.9

41.5

52.7

9.4

39.2

58.1

8.1

36.9

64.1

6.9

44

0

47.4

44.3

12.8

45.3

48.4

11.2

43.0

53.2

9.7

40.7

58.6

8.3

38.3

64.6

7.1

45

0

48.2

44.5

13.0

46.1

48.7

11.4

43.8

53.5

9.8

41.5

58.9

8.5

39.0

64.9

7.2

46

0

49.1

44.7

13.2

46.9

48.9

11.5

44.6

53.7

10.0

42.2

59.1

8.6

39.8

65.2

7.3

48

0

50.8

45.1

13.5

48.6

49.3

11.8

46.2

54.2

10.2

43.8

59.6

8.8

41.2

65.7

7.5

50

0

52.6

45.5

13.9

50.2

49.8

12.1

47.8

54.7

10.5

45.3

60.2

9.0

42.7

66.3

7.7

55

0

57.1

46.6

14.7

54.6

51.0

12.9

52.0

56.0

11.2

49.3

61.5

9.6

46.5

67.7

8.2

60

0

61.8

47.7

15.5

59.1

52.2

13.6

56.4

57.3

11.8

53.5

63.0

10.2

50.5

69.2

8.8

Table PD-8— 60 Ton — CGAF-C60

Table PD-7— 50 Ton — CGAF-C50

Notes:
1. Data based on 0.0001 fouling factor at sea level.
2. Interpolation between points is permissible.
3. Extrapolation beyond points is not permissible.
4. EER - Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, water temperatures below 40°F.
5. Ratings based on evaporator drop of 10°F

condenser fans and control power

6. Rated in accordance with ARI Standard 550/590-98.
7. Minimum recommended ethylene glycol percentage used for leaving water temperatures below 40°F.
8. Use the following equation to calculate COP values at other than ARI conditions, COP = EER x .2928.

(50–60 Ton)
Full Load

Table PD-9 — Coefficient of Performance (COP) and
Integrated Part Load Values (IPLV) at ARI Conditions

Tons

Model Number

IPLV

COP

10

CGA120B

2

12.3

2.9

15

CGA180B

12.9

2.8

20

CGAF-C20

14.8

2.8

25

CGAF-C25

14.6

2.8

30

CGAF-C30

13.9

2.8

40

CGAF-C40

14.9

2.8

50

CGAF-C50

14.5

2.8

60

CGAF-C60

15.0

2.8

Notes:
1. Integrated Part Load Values are EERs in (Btu/watt-hour).
2. CGA120B1 - Single Phase IPLV = 11.4, COP = 2.7

Advertising