102

Table 5-4

Filter Data

Panel-Type Filters

Bag-Type Filters

Cartridge Filters

Panel-Type Prefilters

Unit Model

(Note 1)

(Note 2)

(box-type) (Note 2)

(Note 3)

Qty

Size of each

Qty.

Size of each

Qty.

Size of each

Qty.

Size of each

S_HF-C20 &

12

20 X 20 X 2

4

12 X 24 X 19

4

12 X 24 X 12

4

12 X 24 X 2

C25

3

24 X 24 X 19

3

24 X 24 X 12

3

24 X 24 X 2

S_HF-C30

16

20 X 20 X 2

2

12 X 24 X 19

2

12 X 24 X 12

2

12 X 24 X 2

6

24 X 24 X 19

6

24 X 24 X 12

6

24 X 24 X 2

S_HF-C40

16

20 X 25 X 2

5

12 X 24 X 19

5

12 X 24 X 12

5

12 X 24 X 2

6

24 X 24 X 19

6

24 X 24 X 12

6

24 X 24 X 2

S_HF-C50 &

20

20 X 25 X 2

3

12 X 24 X 19

3

12 X 24 X 12

3

12 X 24 X 2

C55

9

24 X 24 X 19

9

24 X 24 X 12

9

24 X 24 X 2

S_HF-C60,

35

16 X 20 X 2

6

12 X 24 X 19

6

12 X 24 X 12

6

12 X 24 X 2

C70 & C75

8

24 X 24 X 19

8

24 X 24 X 12

8

24 X 24 X 2

S_HG-C90 &

25

24 X 24 X 2

3

12 X 24 X 19

3

12 X 24 X 12

3

20 X 24 X 2

S_HG-D11

15

24 X 24 X 19

15

24 X 24 X 12

15

24 X 24 X 2

S_HG-D12 &

25

24 X 24 X 2

3

12 X 24 X 19

3

12 X 24 X 12

3

20 X 24 X 2

S_HG-D13

15

24 X 24 X 19

15

24 X 24 X 12

15

24 X 24 X 2

Notes:
1. Dimensions shown for “Panel-Type Filters”apply to “Throw away”, “Cleanable Wire Mesh”,
and “High Efficiency Throw away” Filters.
2. S_HF units ordered with “Bag-Type Filters” or “Cartridge Filters” (box-type) include a bank
of “Panel-Type Prefilters”.
3. The same “Panel-Type Prefilters” are used with “Bag-Type” and “Cartridge (box-type)” filters.

Table 5-5

"Wet Heat" Coil Fin Data

Total Coil

Fins

Fins

Coil

Coil

Face Area

per

per

Model

Type

Rows

(sq.ft.)

Foot

Foot

SLHF-C20,

WC

C25 & C30

Prima Flo

2

13.75

80

110

(hot water)

SLHF-C40,

WC

C50 & C55

Prima Flo

2

19.25

80

110

(hot water)

SLHF-C60,

WC

C70 & C75

Prima Flo

2

26.25

80

110

(hot water)

SLHG-C90,

WC

D11, D12

Prima Flo

2

17.5 (2)

80

110

& D13

(hot water)

SSHF-C20,

NS

1

13.75

42

96

C25 & C30

(steam)

SSHF-C40,

NS

1

13.75 (1)

42

96

C50 & C55

(steam)

5.5 (1)

SSHF-C60,

NS

1

18.75 (1)

42

72

C70 & C75

(steam)

7.5 (1)

SLHG-C90,

NS

1

17.5 (2)

52

96

D11, D12

(steam)

& D13

Note: To determine unit heating capacity (i.e., “low heat” or “high heat”),
see Digit 9 of the model number stamped on the unit nameplate.

Service & Maintenance (Continued)

Advertising