Table 4-2 (Continued)

90 through 130 Ton Component Static Pressure Drops (Inches W.C.)

Econ.

CFM

Perm

Bag

Cartridge

Std

With Or

Nom

STD

SEHF/G

Std. High Wire

And

And

Roof Without

Tons

AIR

Wet Dry

Wet Dry

Low High All KW's Low High Low High Fiber Effic. Mesh Prefilter Prefilter Curb Exh. Fan

27,000

.40 .31

.67

.51

N/A .25

.13

.26

.31

.22 .32

.11

.13

N/A

.68

.65

——

.20

32,000

.53 .41

.89

.68

N/A .31

.16

.35

.41

.30 .43

.14

.16

N/A

.84

.84

.31

90

37,000

.67 .52

1.12 .86

N/A .39

.23

.45

.52

.40 .55

.17

.19

N/A

1.02

1.04

.41

42,000

.82 .63

1.36 1.06

N/A .46

.29

.56

.65

.50 .68

.21

.22

N/A

1.19

1.06

.52

45,000

.92 .71

1.53 1.19

N/A .52

.32

.63

.73

.58 .76

.24

.24

N/A

——

——

.63

31,000

.56 .45

.84

.64

N/A .28

.17

.33

.39

.29 .40

N/A

.13

N/A

.82

.80

——

.22

35,000

.68 .54

1.02 .78

N/A .36

.21

.41

.48

.36 .50

N/A

.16

N/A

.96

.96

.32

105 39,000

.81 .65

1.21 .94

N/A .42

.26

.49

.57

.44 .60

N/A

.19

N/A

1.09

1.12

.44

43,000

.94 .76

1.42 1.10

N/A .45

.30

.57

.66

.53 .71

N/A

.22

N/A

1.22

1.30

.54

46,000 1.05 .84

1.58 1.23

N/A .55

.34

.65

.75

.61 .79

N/A

.24

N/A

——

——

.64

31,000

.84 .64

N/A N/A

N/A .28

.17

.33

.39

.29 .40

N/A

.13

N/A

.82

.80

——

.22

115/ 35,000 1.03 .79

N/A N/A

N/A .36

.21

.41

.48

.36 .50

N/A

.16

N/A

.96

.96

.32

130 39,000 1.21 .94

N/A N/A

N/A .42

.26

.49

.57

.44 .60

N/A

.19

N/A

1.09

1.12

.44

43,000 1.42 1.10

N/A N/A

N/A .45

.30

.57

.66

.53 .71

N/A

.22

N/A

1.22

1.30

.54

46,000 1.58 1.23

N/A N/A

N/A .55

.34

.65

.75

.61 .79

N/A

.24

N/A

0

0

.64

Notes:
1. Static pressure drops of accessory components must be added to external static pressure to enter fan selection tables.
2. Gas heat section maximum temperature rise of 60 F.
3. Throwaway filter option limited to 300 ft/min face velocity.
4. Bag filter option limited to 740 ft/min face velocity.
5. Horizontal roof curbs assume 0.50" static pressure drop or double the standard roof curb pressure drop, whichever is greater.
6. No additional pressure loss for model SXHF.
7. 90 - 130 ton roof curbs adds no pressure drop.

Std.

Capacity

Evaporator Coil

SFHF/G

High

SLHF/G

SSHF/G

Throwaway

Filters

Heating System

Table 4-3

90 through 130 Ton 100% Modulating Exhaust Fan Performance

STD

Negative Static Pressure

AIR

0.25" W.G.

0.50" W.G.

0.75" W.G.

1.00" W.G.

1.25" W.G.

1.50" W.G

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

24,000

477

7.04

513

7.95

561

9.29

604

10.66

648

12.15

693

13.83

27,000

530

9.80

558

10.69

597

11.99

639

13.54

677

15.08

716

16.73

30,000

584

13.24

608

14.16

637

15.34

675

16.96

712

18.67

746

20.38

33,000

638

17.42

659

18.39

683

19.53

713

21.02

749

22.88

781

24.75

36,000

693

22.42

711

23.46

732

24.61

756

25.99

786

27.75

818

29.80

40,000

766

30.50

782

31.62

800

32.83

819

34.17

841

35.75

868

37.69

STD

Negative Static Pressure

AIR

1.75" W.G.

2.00" W.G.

2.25" W.G.

2.50" W.G.

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

24,000

737

15.66

781

17.54

823

19.45

862

21.42

27,000

756

18.53

796

20.51

835

22.59

874

24.71

30,000

781

22.18

817

24.10

853

26.19

889

28.42

33,000

812

26.63

844

28.57

877

30.61

910

32.79

36,000

848

31.85

877

33.89

905

35.98

935

38.14

40,000

897

39.94

926

42.24

952

44.50

977

46.77

Note: Blocked areas identify non-standard drive selections.

Advertising