Figure 4-4 (continued) – Trane INTELLIPAK ™ ™ ™ ™ ™ Commercial Single-Zone Rooftop Air Conditioners with CV or VAV Control User Manual

Page 76

Advertising
background image

74

Figure 4-4 (Continued)

40, 50 & 55 Ton Supply Fan Performance with Inlet Guide Vanes

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

0

2000

4000

6000

8000

10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000

CFM

STATIC PRESSURE, Inc

h

e

s

w.c

.

40% w

o

cf

m

50%

60%

70%

1200 RPM

500 RPM

600 RPM

700 RPM

800 RPM

900 RPM

1000 RPM

1100 RPM

5 HP

7.5 HP

10 HP

15 HP

20 HP

25 HP

30 HP

40 HP

S_HFC40, C50, C55
Dual 20 X 20 Fans
Entrance Losses
- with Inlet Guide Vanes
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 7.5
- Maximum Motor HP
C40, C50 & C55 = 30 HP
- Maximum RPM
7.5 - 15 HP = 1141
20 - 30 HP = 1170
- Maximum CFM
C40 = 18,000
C50 = 22,500
C55 = 24,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.

90%

80%

60, 70 & 75 Ton Supply Fan Performance with Inlet Guide Vanes

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

0

3000

6000

9000

12000

15000

18000

21000

24000

27000

30000

33000

36000

CFM

STATIC PRESSURE, Inches w

.c.

S_HFC60, C70, C75
Dual 22 X 22 Fans
Entrance Losses
- with Inlet Guide Vanes
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 10
- Maximum Motor HP = 40
- Maximum RPM = 1130
- Maximum CFM
C60 = 27,000
C70 & C75 = 30,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.

1000 RPM

900 RPM

800 RPM

700 RPM

600 RPM

500 RPM

1100 RPM

1200 RPM

7.5 HP

10 HP

15 HP

20 HP

25 HP

30 HP

40 HP

50 HP

90% wocfm

80%

50%

40%

w

o

c

fm

70%

60%

Advertising